Daikin FAQ100BVV1B [146/381] Simulated operation function

Daikin FAQ100BVV1B [146/381] Simulated operation function
Functional concept ESIEN05-04
2–8 Part 2 Functional Description
3
1
2
4
5
1.5 Simulated Operation Function
Outline When a malfunction on one of the below thermistors occurs, operation will continue while displaying
the applicable alarm on the remote-controller. Fin thermistor malfunction is only displayed when
pressing the "Inspection" button on the remote-controller.
Sensors
Q Outside temperature thermistor
Q Outdoor heat exchanger thermistor
Q Fin thermistor
Q Discharge pipe thermistor
Q Indoor unit air suction thermistor
Q Indoor heat exchanger thermistor
Remark Simulated operation will not be conducted in case the low pressure sensor or suction thermistor is
malfunctioning.