Field Settings ESIEN05-04
4–26 Part 4 Commissioning and Test Run
3
1
4
5
3.8 MAIN/SUB Setting when Using Two remote controls
Situation The MAIN/SUB setting is necessary when one indoor unit is controlled by two remote controls. When
you use two remote controls (control panel and separate remote control), set one to MAIN and the
other to SUB. You can do this by setting the switch on the remote control’s PCB.
Setting The remote controls are factory set to MAIN, so you only have to change one remote control from
MAIN to SUB. To change a remote control from MAIN to SUB, proceed as follows:
Step Action
1 Insert a flathead screwdriver into the recess between the upper and lower part of the
remote control, as shown in the illustration below. Gently pry off the upper part of the con-
troller, working from the two possible positions.
2 Turn the MAIN/SUB changeover switch on the PCB to “S”.
Upper part of the
remote control
Lower part of the
remote control
S
M
S
M
The switch is set to
MAIN (factory setting)
Set the switch to SUB.