Daikin FAQ100BVV1B [169/381] Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred

Daikin FCQ71DV3B [169/381] Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred
ESIEN05-04 Troubleshooting
Part 3 Troubleshooting 3–7
33
4
5
1
Troubleshooting
Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Possibly faulty electric
component
Turn on power switch or replace
fuse.
If high-harmonics circuit breaker
is not used on inverter
compressor, have the circuit
breaker replaced.
Wait until power returns.
Normal. Equipment starts
operation 3 minutes later (3-min
standby).
Diagnose based on error code
on remote controller.
Normal. Equipment starts
operation 3 minutes later (3-min
standby).
Diagnose based on error code
on remote controller.
Check electric system.
Is power
switch OFF or fuse for
power switch
blown?
Is
operation lamp on
LCD remote controller
flashing?
Is
operation switch pressed
repeatedly?
Wireless
remote controller
Is operation lamp on indoor
unit signal receiving
section flashing?
Is
thermostat changed and
reset again?
Is there power failure?
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
(S2575)