Daikin FAQ100BVV1B [214/381] Malfunctioning field setting switch ua

Daikin FAQ100BUV1B [214/381] Malfunctioning field setting switch ua
Error Codes: System Malfunctions ESIEN05-04
4–8 Part 3 Troubleshooting
3
1
3
4
5
1.5 Malfunctioning Field Setting Switch (
UA
)
Error code UA
Error generation The error is generated when incorrect field settings have been set for pair/twin/triple/double twin.
Causes The possible causes are:
Q Malfunctioning indoor or outdoor unit PCB
Q Malfunctioning power supply PCB
Q Indoor-outdoor, indoor-indoor unit transmission wiring
Q Malfunctioning remote control wiring.

Содержание

Скачать