Daikin FAQ100BVV1B [215/381] Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred

Daikin FCQ140DV3B [215/381] Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred
ESIEN05-04 Error Codes: System Malfunctions
Part 3 Troubleshooting 4–9
33
4
5
1
Troubleshooting
Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Connect the remote controller correctly.
Check setting "No. of Connected Twin
System Indoor Units" of indoor unit.
Replace the transformer.
Wiring could be incorrect, recheck.
Connect correctly.
Indoor unit PCB replacement.
Operates normally.
Connect correctly.
Connect correctly.
Set correctly.
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
Is there
220-240 VAC
between No.1 and No.3 of
X2M (indoor Unit)?
Is the power
supply PCB correctly
connected?
Is the
indoor-indoor and
indoor-outdoor jumper
correctly
connected?
Is the
indoor-indoor and
indoor-outdoor jumper
correctly
connected?
Is the
outdoor unit used for
Twin system?
Is the remote
control connected to
more than
one indoor
unit?
Are the
microcomputer normal
monitors (HAP) of all
indoor unit PCB
flashing?
Are the
transmission normal
montiors (HBP) of all
indoor unit PCB
flashing?
Operating normally?
Turn the power off once, then
back on, and restart operation.
Is the setting
of Pair/Twin/Triple set
correctly?