Daikin FAQ100BVV1B [181/381] Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred

Daikin FAQ71BUV1B [181/381] Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred
ESIEN05-04 Troubleshooting
Part 3 Troubleshooting 3–19
33
4
5
1
Troubleshooting
Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Connect correctly.
Connect correctly.
Does the flap swing?
Is continuity/no
continuity reversed?
YES
NO
NO
YES
YES
YES
Replace the indoor unit
PC board.
Replace the swing
motor assembly.
NO
220 - 240 VAC?
NO
YES
NO
(S2577)
Is
the limit
switch’s transfer
connector correctly
connected?
Turn the power supply off once
and back on, and check
whether the swing flap motor
swings when the power supply
is turned back on.
Disconnect X14A, turn the
power supply off once and back
on, and check if the limit switch
has continuity when the power
supply it turned back on.
Turn the power supply off once
and back on, and measure the
output voltage of connector
X29A when the power supply is
turned back on.
Are
the connectors
correctly connected to
X29A and X14A on
the PC board?

Содержание