Daikin FAQ100BVV1B [180/381] Swing flap does not operate

Daikin FUQ125BUV1B [180/381] Swing flap does not operate
Troubleshooting ESIEN05-04
3–18 Part 3 Troubleshooting
3
1
3
4
5
1.3.11 Swing flap does not operate
Applicable Models FUQ, FHQ, FAQ100
Method of
Malfunction
Detection
Utilizes ON/OFF of the limit switch when the motor turns.
Malfunction
Decision
Conditions
When ON/OFF of the micro switch for positioning cannot be reversed even through the swing flap
motor for a specified amount of time (about 30 seconds).
Remark Some functions can force the swing flap into a fixed position, altough swing mode is selected on the
remote control. This is not an unit error, but a control function to prevent draft to the customer.
Before starting the troubleshooting, make sure the swing flap is not forced into such a fixed position.
(e.g. Hot start, defrost operation, thermostat OFF in heating operation or freeze prevention in cooling
operation. For details see "Fan and Flap Operations" on page 2-22 )
Possible Causes
Q Faulty swing motor
Q Faulty micro switch
Q Faulty connector connection
Q Faulty indoor unit PC board