Daikin FAQ100BVV1B [196/381] 34 part 3 troubleshooting

Daikin FUQ71BUV1B [196/381] 34 part 3 troubleshooting
Error Codes ESIEN05-04
3–34 Part 3 Troubleshooting
3
1
3
4
5
Troubleshooting
Remark If "A3" is detected by a PC board which is not mounted with X15A, the PC board is defective.
Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Begin
Is
the unit a
cassette or built-in
type?
Is
a drain
pump connected to
the indoor unit PCB?
Does
the drain pump
work after restarting
operation?
Is the
drain water
level abnormally
high?
Is
the float
switch connected to
X15A?
22
0-240
VAC?
Is
there
continuity?
Is
the
optional drain
raising mechanism
connected?
Is
the
short-circuit
connector connected to X15A
on the indoor unit
PCB?
Connect the
Short-circuit
connector.
Replace the
Short-circuit
connector
Set to
"emergency" and
check the voltage
of X25A.
Replace the
drain pump.
Remove the float switch from
X15A, short-circuit X15A, and
restart operation.
Replace indoor
unit PCB.
There is a malfunction
of the drain system.
Replace float
switch.
Replace the
indoor unit PCB.
Connect
float switch
Connect the
drain pump.
Replace indoor
unit PCB.
Check the continuity of the
short-circuit connector.
No
Yes
Yes
Yes
Yes Yes
Yes
Yes
Yes
Yes
No No
Yes
No
No
No
No No
No
No
Yes
Does "A3"
appear on the remote
controller display?