Daikin FXSQ32P7VEB [110/370] For systems with multi outdoor units the control shown below is conducted by outdoor unit

Daikin FXSQ20P7VEB [110/370] For systems with multi outdoor units the control shown below is conducted by outdoor unit
Protection Control SiBE311209
101 Function
[In heating operation]
+
For systems with multi outdoor units, the control shown below is conducted by outdoor
unit.
Normal operation
Pe < 0.17
MPa
&
• Pe > 0.23MPa
• Compressor step = Max. step
INV. compressor (see 2):
3 steps down per 10 sec.
&
• Pe > 0.20MPa
• A lapse of 15 sec.
&
• Pe < 0.17MPa
• A lapse of 10 sec.
INV. compressor (see 2):
1 step up per 15 sec.
Pe: Value detected by the low
pressure sensor by each
outdoor unit.
2: For INV. compressor steps,
refer to information on P.92
and 93.
&
• Pe < 0.13MPa
A lapse of 10 sec.
STD compressor 2:
OFF
&
• Pe < 0.13MPa
A lapse of 10 sec.
&
• Pe < 0.13MPa
A lapse of 10 sec.
STD compressor 1:
OFF
INV. compressor:
52 Hz
Pe < 0.12MPa
Pe > 0.17MPa
Hot gas solenoid valve (Y1S):
ON
Pe < 0.07MPa
Low pressure standby occurs
4 times in a period of 60 min.
Restart standby
(3 times per 60 min. at maximum)
Stop due to error
(
E4
displayed)