Daikin FXSQ32P7VEB [326/370] Master unit centralized connector setting table the master unit centralized setting connector cn1 x1a is mounted at the factory to independently use a single unit of the intelligent touch controller or a single unit of the central remote controller do not dismount the master unit centralized setting connector i e use the connector with the factory setting unchanged to independently use the schedule timer insert an independent use setting connector no independent use setting connector has been mounted at the factory insert the connector which is attached to the casing of the master unit in the pcb cn1 x1a independent use connector master unit centralized setting connector to use two or more centralized controller in combination make settings according to the table shown below

Daikin FXZQ25M9V1B [326/370] Master unit centralized connector setting table the master unit centralized setting connector cn1 x1a is mounted at the factory to independently use a single unit of the intelligent touch controller or a single unit of the central remote controller do not dismount the master unit centralized setting connector i e use the connector with the factory setting unchanged to independently use the schedule timer insert an independent use setting connector no independent use setting connector has been mounted at the factory insert the connector which is attached to the casing of the master unit in the pcb cn1 x1a independent use connector master unit centralized setting connector to use two or more centralized controller in combination make settings according to the table shown below
Troubleshooting by Indication on the Remote Controller SiBE311209
317 Service Diagnosis
Master Unit Centralized Connector Setting Table
The master unit centralized setting connector (CN1/X1A) is mounted at the factory.
To independently use a single unit of the intelligent Touch Controller or a single unit of the
central remote controller, do not dismount the master unit centralized setting connector (i.e.,
use the connector with the factory setting unchanged).
To independently use the schedule timer, insert an independent-use setting connector.
No independent-use setting connector has been mounted at the factory. Insert the
connector, which is attached to the casing of the master unit, in the PCB (CN1/X1A).
(Independent-use connector = Master unit centralized setting connector)
To use two or more centralized controller in combination, make settings according to the
table shown below.
Note:
1. The intelligent Touch Controller and the schedule timer are not available for combined use.
2. The intelligent Touch Controller, central remote controller, and the unified ON/OFF controller have been
set to "Provided with the master unit centralized setting connector" at the factory. The schedule timer
has been set to "Not provided with the master unit centralized setting connector" at the factory, which is
attached to the casing of the master unit.
CHECK 14
Centralized controller connection pattern Setting of master unit centralized setting connector (2)
× (1)
1 unit
1 unit
× (1)
Provided Not provided
× (1)
× (1)
1 unit Not provided
1 unit Not provided
1 unit Not provided
1 unit Provided
intelligent
Touch
Controller
Central
remote
controller
Unified
ON/OFF
controller
Schedule
timer
intelligent
Touch
Controller
Central
remote
controller
Unified
ON/OFF
controller
Schedule
timer
Only a
single unit:
"Provided",
Others: "Not
provided"
Only a
single unit:
"Provided",
Others: "Not
provided"
All "Not
provided"
Only a
single unit:
"Provided",
Others: "Not
provided"
All "Not
provided"
Only a
single unit:
"Provided",
Others: "Not
provided"
1 to 16
units
1 to 16
units
1 to 8
units
1 to 4
units
1 to 2
units
1 to 2
units
Pattern
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)