Daikin FXSQ32P7VEB [289/370] Refer to p 07

Daikin FXSQ50PVE4 [289/370] Refer to p 07
SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 280
Refer to P.307.
Turn ON the power supply,
and then press the ON button.
The system enters standby
mode before the outdoor unit
fan starts rotating.
YES
NO
The system enters standby mode
before the compressor completes
startup sequence.
YES
NO
The error "
U2
"
recurs.
YES
NO
Replace the inverter PCB.
(Defective noise filter)
Replace the inverter PCB.
If the inverter PCB
significantly gets damaged,
check for the compressor.
Check for all wirings.
Continue the operation.
External factors such as
instantaneous power failure
are supposed.
Is the power transistor
normal?
YES
Connect and disconnect the
following connectors.
(1) X15A (A2P) X20A (A1P)
(2) X6A (A4P) X28A (A1P)
The inverter PCB
gets damaged.
YES
NO
A
Replace the inverter PCB.
Replace the inverter PCB.
If the inverter PCB significantly
gets damaged, the compressor
or the fan motor may have
caused a failure.
CHECK 4
CHECK 4