Daikin FXSQ32P7VEB [223/370] Indoor unit fan motor abnormality

Daikin FXSQ40PVE [223/370] Indoor unit fan motor abnormality
SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 214
Indoor Unit Fan Motor Abnormality
Remote
Controller
Display
A6
Applicable
Models
FXHQ32~100MAVE, FXDQ20~32PB, 40~63NBVE
Method of Error
Detection
This error is detected if there is no revolutions detection signal output from the fan motor.
Error Decision
Conditions
When no revolutions can be detected even at the maximum output voltage to the fan
Supposed
Causes
Defective indoor unit fan motor
Broken wires
Defective contact
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Properly connect the connectors.
(At this time, check for any
defective connector contact or
broken wires.)
Check the indoor unit fan motor
and the wiring circuits of the
motor.
Replace the indoor unit PCB.
Are the X4A and
X27A connectors
securely connected?
Is the power of approx.
12VDC supplied between
the Pins1 and 3 when the
X27A is disconnected and
the power supply turns
ON?
NO
YES
YES
NO