Daikin FXSQ32P7VEB Сервис мануал онлайн [224/370] 544690

Daikin FXZQ50MVE4 Сервис мануал онлайн [224/370] 542853
Troubleshooting by Indication on the Remote Controller SiBE311209
215 Service Diagnosis
Remote
Controller
Display
A6
Applicable
Models
FXMQ50~140P
Method of Error
Detection
Detection from the current flow on the fan PCB
Detection from the RPM of the fan motor in operation
Detection from the position signal of the fan motor
Detection from the current flow on the fan PCB when the fan motor starting operation
Error Decision
Conditions
An overcurrent flows.
The RPM is less than a certain level for 6 seconds.
A position error in the fan rotor continues for 5 seconds or more.
An overcurrent flows.
Supposed
Causes
The clogging of a foreign matter
The disconnection of the fan motor connectors (X1A and X2A)
The disconnection of the connectors between the indoor unit PCB (A1P) and fan PCB (A2P)
A failure in fan PCB (A2P)
A failure in the fan motor