Daikin FXSQ32P7VEB [99/370] Normal operation

Daikin FXZQ25M9V1B [99/370] Normal operation
SiBE311209 Normal Operation
Function 90
6. Normal Operation
6.1 List of Functions in Normal Operation
6.1.1 Outdoor Unit
6.1.2 Function Unit
6.1.3 Indoor Unit
*1: Refer to “6.3 Electronic Expansion Valve PI Control” on P.94.
Part Name Symbol
Electric
Symbol
Normal Cooling Normal Heating
Compressor 1
M1C
PI control, High pressure protection,
Low pressure protection,
Td protection, INV protection,
PI control, High pressure protection,
Low pressure protection,
Td protection, INV protection,
Compressor 2 M2C
Compressor 3 M3C
Outdoor unit fan 1
M1F
Cooling fan control Fan step No.7 or No.8
Outdoor unit fan 2 M2F
Electronic expansion valve
(Main)
EVM Y1E 480 pls PI control
Electronic expansion valve
(Subcooling)
EVT Y3E PI control PI control
Electronic expansion valve
(Refrigerant charge)
EVJ Y2E 80 pls 80 pls
Solenoid valve (Refrigerant
regulator gas vent pipe)
SVG Y1S ON for refrigerant recovery ON for refrigerant recovery
Four way valve
(Heat exchanger switch)
20SA Y3S OFF ON
Solenoid valve (Refrigerant
regulator liquid pipe)
SVL Y4S ON for refrigerant recovery ON for refrigerant recovery
Solenoid valve (Hot gas) SVP Y5S OFF OFF
Solenoid valve (Main bypass)
SVE Y6S ON OFF
Solenoid valve (Refrigerant
regulator discharge pipe)
SVO Y7S ON for refrigerant discharge ON for refrigerant discharge
Solenoid valve (Refrigerant
regulator discharge pipe)
SVT Y8S ON for oil level control ON for oil level control
Solenoid valve (Heat
exchanger hot gas)
SVHG Y9S ON
A lapse of 10 min. after defrost and
Ta < 0: ON
Conditions other than above
condition
Four way valve (High/low
pressure gas pipe switch)
20SB Y2S ON OFF
Part name Electric symbol Cooling operation
Heating operation
Normal
Low outdoor air temp.
Compressor M1C OFF OFF PI control
Cooling fan M1F OFF OFF Cooling fan control
Electronic
expansion valve
Liquid injection Y1E 0 pls 0 pls
Discharge
superheated
degree control
Two-stage
switching-1
Y2E1 0 pls 0 pls 760 pls (fully open)
Two-stage
switching-2
Y2E2 0 pls 0 pls 760 pls (fully open)
Solenoid valve
Hot gas Y1S OFF OFF OFF
Two-stage
decompression
Y2S OFF OFF ON
Bypass-1 Y3S ON ON OFF
Bypass-2 Y4S ON ON OFF
Liquid line switch Y5S OFF ON OFF
Indoor unit actuator Normal cooling Normal heating
Fan M1F
Thermostat ON unit Remote controller setting Remote controller setting
Stopping unit OFF OFF
Thermostat OFF unit Remote controller setting LL
Electronic
expansion
valve
Y1E
Thermostat ON unit Normal opening
1 Normal opening
1
Stopping unit 0 pls 192 pls
Thermostat OFF unit 0 pls 192 pls