1.3.5 Remaining Refrigerant Charging Method
When the leak detection function is not required and the entire refrigerant quantity can not be
charged through the liquid pipe stop valve service port with the unit not operating (refer to Pre-
charging” on P.134), make sure to charge the remaining charging quantity using the following
procedure:
1. Turn the power of the indoor unit, the BS unit and the outdoor unit ON.
2. Make sure to open the stop valves of the suction gas pipe, the high pressure/low pressure
gas pipe and the liquid pipe completely.
3. Connect the refrigerant charge hose to the refrigerant charging port (for additionally
charging).
4. When the unit is not operating, press the BS2 SET button until the additional refrigerant
charging operation function A in setting mode 2 can be defined the H1P LED is on (
k
).
5. The operation starts automatically.
The H2P LED will start blinking (
l
) and the messages "Test operation" and "Under
centralized control" will display on the remote controller.
6. After charging the specified quantity of refrigerant, press the BS3 RETURN button to stop
the operation.
The operation will stop within 30 minutes.
If charging is not completed after 30 minutes, set and perform the additional refrigerant
charging operation again.
If the additional refrigerant charging operation stops before the passing of 30 minutes,
the system may be overcharged.
Never charge extra refrigerant.
7. Disconnect the refrigerant charge hose.
8. Are the stop valves for both liquid and gas open?
Is the amount of refrigerant, that has been added, recorded on the refrigerant charge label?