Daikin FXSQ32P7VEB [236/370] Suction air thermistor r1t abnormality

Daikin FXZQ25M9V1B [236/370] Suction air thermistor r1t abnormality
Troubleshooting by Indication on the Remote Controller SiBE311209
227 Service Diagnosis
4.11 Suction Air Thermistor (R1T) Abnormality
C9
Applicable
Models
All indoor unit models
Method of Error
Detection
Error detection is carried out by temperature detected by suction air thermistor.
Error Decision
Conditions
When the suction air thermistor becomes disconnected or shorted while the unit is running
Supposed
Causes
Defective indoor unit thermistor (R1T) for suction air
Defective indoor unit PCB
Troubleshooting
Refer to P.314.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
Normal (The error is caused by
defective contact.)
YES
YES
NO
Remove the thermistor from
the indoor unit PCB, and then
insert it again.
Replace the thermistor (R1T).
Replace the indoor unit PCB.
Remove the thermistor from the
indoor unit PCB, and then make
resistance measurement of the
thermistor using a multiple
meter.
Is the thermistor
normal?
5 k to 90 k
CHECK 11
CHECK 11