Daikin FXSQ32P7VEB [112/370] Inverter protection control

Daikin FXSQ40PVE [112/370] Inverter protection control
Protection Control SiBE311209
103 Function
7.4 Inverter Protection Control
Inverter current protection control and radiation fin temperature control are performed to prevent
tripping due to an error, or transient inverter overcurrent, and fin radiation temperature increase.
In the case of multi-outdoor-unit system, each INV compressor performs these controls in
the following sequence.
7.4.1 Inverter Overcurrent Protection Control
This control is conducted by each INV. compressor.
7.4.2 Radiation Fin Temperature Control
This control is conducted by each INV. compressor.
Normal operation
Inverter current > B
&
• Inverter current < B
• Upper limit of compressor operating frequency = 210 Hz
INV. compressor (see
1):
1 step down per 10 sec.
Inverter current < B continues for
a period of consecutive 20 sec.
INV. compressor (see
1):
1 step up per 20 sec.
&
• Inverter current >B
• A lapse of 10 sec.
Inverter current > C continues for a
period of consecutive 260 sec.
Occur 4 times per 60 min.
1: For INV. compressor steps, refer
to information on P.92 and 93.
2: For values B and C, refer to the
table shown below.
BC
Outdoor unit 14.7A 16.1A
Function unit 14.7A 16.1A
Restart standby:
(3 times per 60 min. at maximum)
Stop due to error
(“
L8
” displayed)
Normal operation
Tfin 84°C
(1)
&
• Tfin < 81°C
• Upper limit of compressor operating frequency = 210 Hz
Tfin 81°C continues for
a period of consecutive 3 min.
INV. compressor (see
2):
1 step down per 10 sec.
INV. compressor (see
2):
1 step up per 3 min.
&
• Tfin 84°C
• A lapse of 10 sec.
Tfin > 93°C
Occur 4 times per 60 min.
1: Tfin: Value detected by the
radiation fin thermistor.
2: For INV. compressor steps,
refer to information on P.92
and 93.
Restart standby:
(3 times per 60 min. at maximum)
Stop due to error
(“
L4
” displayed)