113 Function
8.4 Emergency Operation
If any of the compressors goes wrong, disable the relevant compressor or the relevant outdoor
unit from operating, and then conduct emergency operation only with operational compressors
or outdoor units.
There are 2 ways of conducting the Emergency operation : with remote controller reset and
by setting outdoor unit PCB.
Emergency operation by resetting remote controller
[Emergency operation method]
Reset the remote controller (i.e., press the ON/OFF button on the remote controller for 4
seconds or more) when the outdoor unit stops because of malfunction state.
[Details of operation]
Automatically disable the defective outdoor unit from operating, and then operate other
outdoor units. (This emergency operation is not possible in the system with one outdoor
unit.)
Emergency operation by setting outdoor unit PCB
[Setting Procedure]
Make setting of compressor to be set to "Operation prohibited" while in field setting mode
(Setting mode 2).
Make setting of outdoor unit to be set to "Operation prohibited" while in field setting mode
(Setting mode 2).
(For detail of the setting procedure, refer to information on P.184 to 186.)
[Operation]
Prohibit the compressor that is "set to Operation Prohibited" from operating, and only
operate other compressor(s).
Prohibit the outdoor unit that is "set to Operation Prohibited" from operating, and only
operate other out door unit(s).
Operating method
Applicable model
Emergency operation with
remote controller reset
(Auto backup operation)
Emergency operation with
outdoor unit PCB setting
(Manual backup operation)
RTSYQ10 ~ 16PAY1
Backup operation by the
compressor
RTSYQ20PAY1
Backup operation by the
outdoor unit
Backup operation by the
outdoor unit