Daikin FXSQ32P7VEB [297/370] Troubleshooting

Daikin FXHQ32MAVS [297/370] Troubleshooting
SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 288
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Confirmation of
error 3
Diagnosis Flow 2
Confirmation of
error 4
Unified
changeover the
cooling/heating.
NO
YES
Setting of cooling/heating
selector for the external control
adaptor for outdoor unit is “Slave
unified”.
YES
NO
Setting of cooling/heating
selector for the external
control adaptor for outdoor
unit is “Master in unified”.
NO
YES
Check if the normal
condition monitor LED for
the outdoor unit main
PCB blinks.
NO
YES
Check if the
outdoor unit is
powered ON.
NO
YES
Check if the normal
condition monitor LED for
the external control adaptor
for outdoor unit blinks.
NO
YES
Check if the power supply wiring
for the external control adaptor
for outdoor unit is connected to
5V supply line.
NO
YES
Set the cooling/heating selector
of the external control adaptor
for outdoor unit to “individual”.
Then check if the error occurs
again.
NO
YES
Set the cooling/heating selector of
the external control adaptor for
outdoor unit to “individual”.
The unified addresses for cooling/
heating within the outdoor/outdoor
transmission are duplicated. Set
the address again.
Replace the outdoor unit main
PCB (A1P).
Supply power to the outdoor unit.
Replace the outdoor unit main
PCB (A1P).
Connect the power supply wiring
for the external control adaptor for
outdoor unit to 5V supply line.
Replace the PCB of the external
control adaptor for outdoor unit.
Replace the outdoor unit main
PCB
(
A1P
)
.