Daikin FXSQ32P7VEB [268/370] Low pressure sensor abnormality

Daikin FXHQ100MVE [268/370] Low pressure sensor abnormality
Troubleshooting by Indication on the Remote Controller SiBE311209
259 Service Diagnosis
4.34 Low Pressure Sensor Abnormality
Remote
Controller
Display
JC
Applicable
Models
Outdoor Unit: RTSQ8~16PAY1
Method of Error
Detection
Error is detected from the pressure detected by the low pressure sensor.
Error Decision
Conditions
When the low pressure sensor is short circuit or open circuit
(Not less than 1.77MPa, or -0.01MPa and below)
Supposed
Causes
Defective low pressure sensor system
Connection of high pressure sensor with wrong connection.
Defective outdoor unit PCB.
Defective connection of low pressure sensor
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Are the characteristics of the low
pressure sensor normal? (Make
a comparison between the
voltage characteristics (1) and
the gauge pressure.)
NO
Replace the low pressure sensor.
Confirm which high pressure
sensor is abnormal using
outdoor unit "monitor mode".
1. Set the low pressure gauge
upright.
2. Connect the checker for
VRV to the gauge.
If the PCB pressure
detection normal? (Make a
comparison between the
checker pressure data and
the voltage characteristics
(1).)
Reset the operation, and then
restart the outdoor unit.
Are the
characteristics of
the low pressure
sensor normal?
Replace the outdoor unit main
PCB.
Replace the low pressure sensor.
Replace the outdoor unit main
PCB.
NO
NO
YES
YES
YES