Daikin FXSQ32P7VEB [237/370] Discharge air thermistor r4t abnormality

Daikin FXSQ25PVE [237/370] Discharge air thermistor r4t abnormality
SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 228
4.12 Discharge Air Thermistor (R4T) Abnormality
Remote
Controller
Display
CA
Applicable
Models
FXMQ-P
Method of Error
Detection
Error detection is carried out by temperature detected by discharge air thermistor.
Error Decision
Conditions
When the discharge air thermistor becomes disconnected or shorted while the unit is running
Supposed
Causes
Defective indoor unit thermistor (R4T) for discharge air
Defective indoor unit PCB
Troubleshooting
Refer to P.314.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Remove the thermistor from
the indoor unit PCB, and then
insert it again.
YES
NO
Is the
thermistor
normal?
Remove the thermistor from
the indoor unit PCB, and then
make resistance measurement
of the thermistor using a
multiple meter.
NO
YES
5 k to 90 k
Normal (The error is caused by
defective contact.)
Replace the thermistor (R4T).
Replace the indoor unit PCB.
CHECK 11
CHECK 11