1. Refrigerant Circuit
1.1 RTSQ8PAY1
No. in
refrigerant
system
diagram
Electric
Symbol
Name Major Function
M1C Inverter compressor
Inverter compressor is operated on frequencies between 52Hz and 280Hz by using
the inverter.
Compressor operation steps : Refer to P.92~93.
M1F Inverter fan
Because the system is an air heat exchange type, the fan is operated at 9-step rotation
speed by using the inverter.
Y1E
Electronic expansion valve
(Main: EVM)
While the outdoor unit heat exchanger is evaporator, PI control is applied to keep the
outlet superheated degree of air heat exchanger constant.
Y2E
Electronic expansion valve
(Refrigerant charge EVJ)
This is used to open/close refrigerant charge port.
Y3E
Electronic expansion valve
(Subcooling: EVT)
PI control is applied to keep the outlet superheated degree of subcooling heat
exchanger constant.
Y1S
Solenoid valve (Refrigerant
regulator gas vent pipe: SVG)
This is used to collect refrigerant to the refrigerant regulator.
Y2S
Four way valve (Dual pressure
gas pipe switch: 20SB)
This is used to switch dual pressure gas pipe to high pressure or low pressure.
Y3S
Four way valve (Heat
exchanger switch: 20SA)
This is used to switch outdoor unit heat exchanger to evaporator or condenser.
Y4S
Solenoid valve (Refrigerant
regulator liquid pipe: SVL)
This is used to collect refrigerant to the refrigerant regulator.
 Y5S Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.
 Y6S
Solenoid valve (Main bypass:
SVE)
This opens in cooling operation.
 Y7S
Solenoid valve (Refrigerant
regulator discharge pipe: SVO)
This is used to discharge refrigerant from the refrigerant regulator.
 Y8S
Solenoid valve (Discharge
pipe of refrigerant regulator:
SVT)
Bypass the high pressure gas to the refrigerant regulator.
 Y9S
Solenoid valve (Hot gas:
SVHG)
Bypass the high pressure gas to the outdoor unit heat exchanger.
 S1NPH High pressure sensor Used to detect high pressure.
 S2NPL Low pressure sensor Used to detect low pressure.
 S1PH
High pressure switch (For
INV. compressor)
This functions when the pressure increases to stop operation and avoid high pressure
increase in the fault operation.

Pressure regulating valve
(Liquid pipe)
This is used when pressure increases, to prevent any damage on components caused
by pressure increase in transport or storage.

Pressure regulating valve
(Refrigerant regulator)
This is used when pressure increases, to prevent any damage on components caused
by pressure increase in transport or storage.
 Subcooling heat exchanger Apply subcooling to liquid refrigerant.
 Refrigerant regulator Surplus refrigerant is held according to the operation conditions.
 Capillary tube
Used to return the refrigerating oil separated through the oil separator to the INV.
compressor.
 Capillary tube This is used to discharge refrigerant from the refrigerant regulator.
 R1T Thermistor (Outdoor air: Ta)
Used to detect outdoor air temperature, correct discharge pipe temperature, and
others.
 R2T
Thermistor (Heat exchanger
gas pipe: Tg)
This detects temperature of gas pipe for air heat exchanger. Used to exercise the
constant control of superheated degree when an evaporator is used for outdoor unit
heat exchanging.
 R31T
Thermistor (INV. discharge
pipe: Tdi)
Used to detect discharge pipe temperature. Used for compressor temperature
protection control.
 R4T
Thermistor (Heat exchanger
deicer: Tb)
This detects temperature of some of the liquid pipes for air heat exchanger. Used to
make judgements on defrosting operation.
 R5T
Thermistor (Subcooling heat
exchanger gas pipe: Tsh)
This detects temperature of gas pipe on the evaporator side for the subcooling heat
exchanger. Used to exercise the constant control of superheated degree at the outlet
of subcooling heat exchanger.
 R6T
Thermistor (Subcooling heat
exchanger liquid pipe: Tl)
This detects temperature of liquid pipe between the main electronic expansion valve
and subcooling heat exchanger.
 R7T
Thermistor (Heat exchanger
liquid pipe: Tf)
This detects temperature of liquid pipe between the air heat exchanger and main
electronic expansion valve. Used to make judgements on the recover or discharge
refrigerants to the refrigerant regulator.
 R8T
Thermistor (Suction pipe: TsA)
Used to detect suction pipe temperature.
 R9T Thermistor (Liquid pipe: Tsc)
This detects temperature of liquid pipe between the liquid stop valve and subcooling
heat exchanger.