Daikin FXSQ32P7VEB [70/370] Function unit

Daikin FXSQ100PVE4 [70/370] Function unit
Refrigerant Circuit SiBE311209
61 Refrigerant Circuit
1.5 Function Unit
BTSQ20P
No.
Electric
Symbol
Name Function
M1C Inverter compressor
Inverter compressor is operated on frequencies between 52Hz and
280Hz by using the inverter. Compressor operation steps: Refer to
P.93.
Y1E
Electronic expansion valve (Liquid
injection)
Used to conduct PI control so that the discharge pipe superheated
degree of the compressor will be kept constant.
Y2E1
Electronic expansion valve (Two-
stage selection-1)
Open (fully open) to conduct heating operation at low outdoor air
temperatures (while in two-stage compression mode).
Y2E2
Electronic expansion valve (Two-
stage selection-2)
Y1S Solenoid valve (Hot gas)
Used to prevent transitional suction pressure drops by hot gas
injection.
Y2S
Solenoid valve (Two-stage
pressure reduction)
Open to conduct heating operation at low outdoor air temperatures
(while in two-stage compression mode).
Y3S Solenoid valve (Bypass 1)
Open to conduct cooling operation or normal heating operation (while
in single-stage compression mode).
Y4S Solenoid valve (Bypass 2)
Y5S
Solenoid valve (Liquid line
selection)
Open to conduct normal heating operation (while in single-stage
compression mode).
 S1NPH High pressure sensor Used to detect high pressure.
 S1PH High pressure switch
Activated when pressure rises to stop operation, in order to prevent
high pressure from rising in case of a malfunction.
 Capillary tube
Used to return refrigeration oil separated through the oil separator to
the INV. compressor.
 Capillary tube Used to prevent liquid sealing when operation stops.
 R3T Discharge pipe thermistor Used to detect discharge pipe temperature.
 R4T Liquid temperature thermistor
Used to detect the equivalent saturation temperature of intermediate
pressure while in two-stage compression mode.
Service port
Filter
To
indoor
unit
Gas pipe
Service port
Liquid pipe
Filter
 High pressure
sensor
S1NPH
 High pressure switch
S1PH

Compressor
INV
 Capillary tube
Check
valve
Electronic
expansion valve
Solenoid valve
Check
valve
Filter
Filter
 Capillary tube
Oil separator
Solenoid valve
SV
Solenoid valve
SV
Electronic
expansion valve
Electronic
expansion valve
Check valve
Filter
Gas pipe
To
outdoor
unit
Check valve
Solenoid
valve
Check
valve
Filter
Liquid pipe
Solenoid valve
SV
Check valve

Check valve
Filter
Gas and
liquid
separator
SV
SV
C: 3D060823