Daikin FXSQ32P7VEB [163/370] Caution 1 the air conditioner starts operation suddenly after power failure reset or the main power supply turned on again consequently the user might be surprised with question for the reason why 2 in the service work for example turning off the main power switch during the unit is in operation and turning on the switch again after the work is completed start the unit operation the fan rotates

Daikin FXZQ40M9V1B [163/370] Caution 1 the air conditioner starts operation suddenly after power failure reset or the main power supply turned on again consequently the user might be surprised with question for the reason why 2 in the service work for example turning off the main power switch during the unit is in operation and turning on the switch again after the work is completed start the unit operation the fan rotates
SiBE311209 Field Setting
Test Operation 154
(11) Auto Restart after Power Failure Reset
For the air conditioners with no setting for the function (same as factory setting), the units will be
left in the stop condition when the power supply is reset automatically after power failure reset
or the main power supply is turned on again after once turned OFF. However, for the air
conditioners with the setting (same as factory setting), the units may start automatically after
power failure reset or the main power supply turned ON again (return to the same operation
condition as that of before power failure).
For the above reasons, when the unit is set enabling to utilize “Auto restart function after power
failure reset”, utmost care should be paid for the occurrence of the following situation.
(12) Airflow when Cooling Thermostat is OFF
This is used to set airflow to "LL airflow" when cooling thermostat is OFF.
(13) Setting of Normal Airflow
Make the following setting according to the ceiling height. The second code No. is set to “01” at
the factory.
In the Case of FXAQ
In the Case of FXHQ
In the Case of FXFQ25~80 (All round outlet)
Caution 1. The air conditioner starts operation suddenly after power failure reset or
the main power supply turned ON again. Consequently, the user might be
surprised (with question for the reason why).
2. In the service work, for example, turning OFF the main power switch
during the unit is in operation, and turning ON the switch again after the
work is completed start the unit operation (the fan rotates).
Mode No. First Code No. Second Code No. Contents
12 (22) 6
01 LL airflow
02 Preset airflow
Mode No. First Code No.
Second Code
No.
Setting
13(23) 0
01 Wall mounted type: Standard
02 Wall mounted type: Slight increase
03 Wall mounted type: Normal increase
Mode No. First code No.
Second code
No.
Ceiling height (m)
13(23) 0
01 2.7 or less
02 2.7 - 3.5
Mode
No.
First
code
No.
Second
code
No.
Setting Ceiling height (m)
13 (23) 0
01
Standard · All
round outlet
2.7
02 High Ceiling (1) 2.7 - 3
03 Higher Ceiling (2) 3 - 3.5