Daikin FXSQ32P7VEB [235/370] Gas pipes thermistor r3t abnormality

Daikin FXHQ100MVE [235/370] Gas pipes thermistor r3t abnormality
SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 226
4.10 Gas Pipes Thermistor (R3T) Abnormality
Remote
Controller
Display
C5
Applicable
Models
All indoor unit models
Method of Error
Detection
Error detection is carried out by temperature detected by gas pipe thermistor.
Error Decision
Conditions
When the gas pipe thermistor becomes disconnected or shorted while the unit is running
Supposed
Causes
Defective indoor unit thermistor (R3T) for gas pipe
Defective indoor unit PCB
Troubleshooting
Refer to P.314.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
Normal (The error is caused by
defective contact.)
YES
YES
NO
Remove the thermistor from
the indoor unit PCB, and then
insert it again.
Replace the thermistor (R3T).
Replace the indoor unit PCB.
Remove the thermistor from the
indoor unit PCB, and then make
resistance measurement of the
thermistor using a multiple
meter.
Is the thermistor
normal?
5 k to 90 k
CHECK 11
CHECK 11