Daikin FXSQ32P7VEB [119/370] 1 in case of multi outdoor unit system master unit it conducts the operation listed in the table above slave units operating units conduct the operation listed in the table above non operating units conduct the operation listed in the table above after the oil returning process non operating units stop while in preparation mode

Daikin FXZQ25M9V1B [119/370] 1 in case of multi outdoor unit system master unit it conducts the operation listed in the table above slave units operating units conduct the operation listed in the table above non operating units conduct the operation listed in the table above after the oil returning process non operating units stop while in preparation mode
SiBE311209 Special Control
Function 110
1: In case of multi outdoor unit system:
Master unit: It conducts the operation listed in the table above.
Slave units: Operating units conduct the operation listed in the table above.
Non-operating units conduct the operation listed in the table above after the "Oil returning" process.
(Non-operating units stop while in "Preparation" mode.)
<Function unit>
<Indoor Unit>
Actuator
Electric
Symbol
In preparation
In oil return
operation
After oil return
operation
Step 1 Step 2
Compressor M1C 0 Hz 0 Hz 210 Hz52 Hz 0 Hz
Electronic
expansion valve
(Liquid injection)
Y1E 0 pls 0 pls 0 pls 0 pls
Electronic
expansion valve
(Two-stage
selection 1)
Y2E1 200 pls 0 pls 0 pls 200 pls
Electronic
expansion valve
(Two-stage
selection 2)
Y2E2 200 pls 0 pls 0 pls 200 pls
Solenoid valve
(Hot gas)
Y1S OFF ON ON OFF
Solenoid valve
(Two-stage
decompression)
Y2S OFF OFF OFF OFF
Solenoid valve
(Bypass 1)
Y3SONONONON
Solenoid valve
(Bypass 2)
Y4SONONONON
Solenoid valve
(Liquid line
selection)
Y5SONONONON
Ending Conditions 170 sec.
After
a lapse
of 1 min.
Pc - Pe
< 0.5MPa
After
a lapse
of 4 min.
TsA - Te
< 5°C
After
a lapse
of 1 min.
Pc - Pe
< 0.5MPa
Part Name Electric Symbol Indoor unit actuator operation during heating oil return operation
Fan M1F
Thermo. ON unit OFF
Unit not in operation OFF
Thermo. OFF unit OFF
Electronic
expansion valve
Y1E
Thermo. ON unit Oil return EV degree
Unit not in operation 256 pls
Thermo. OFF unit Oil return EV degree
OR
OR OR