Daikin FXSQ32P7VEB [321/370] List of inverter related error codes

Daikin FXZQ50MVE9 [321/370] List of inverter related error codes
SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 312
List of Inverter-related Error Codes
Code Name Condition for determining error Major cause
Compressor current
L5
Instantaneous overcurrent of
inverter compressor
Inverter output current exceeds 32.3A even
instantaneously.
Liquid sealing
Defective compressor
Defective inverter PCB
L8
Overcurrent of inverter
compressor (Electronic thermal)
Compressor overload running
An overcurrent of 19.0A or more continues for
a period of 5 consecutive seconds or that of
16.1A or more continues for a period of 260
consecutive seconds.
For 230V units:
A current of 33.5A or more continues for a
period of consecutive 5 sec. or that of 27.6A or
more continues for a period of consecutive
260 sec.
The inverter loses synchronization.
Back-flow of compressor liquid
Sudden changes in loads
Disconnected compressor wiring
Defective inverter PCB
Protection device and others
L1
Defective inverter PCB No output is given. Defective heavy current part of
compressor
L9
Defective startup of inverter
compressor
The compressor motor fails to startup. Liquid sealing or defective
compressor
Excessive oil or refrigerant
Defective inverter PCB
E5
Inverter compressor lock The compressor is in the locked status (does
not rotate).
Defective compressor
L4
Radiation fin temperature rise The radiation fin temperature reaches 87°C or
more (while in operation).
Defective fan
Running in overload for an
extended period of time
Defective inverter PCB
U2
Power supply voltage error The inverter power supply voltage is high or
low.
Power supply error
Defective inverter PCB
P1
Imbalanced power supply Power supply voltages get significantly
imbalanced among 3 phases.
Power supply error (imbalanced
voltages of 2% or more)
Defective inverter PCB
Dead inverter PCB
LC
Transmission error (between
inverter PCB and service monitor
PCB)
With the outdoor unit PCB, no
communications are carried out across
service monitor PCB - inverter PCB - fan PCB.
Broken wire in communication
line
Defective service monitor PCB
Defective inverter PCB
Defective fan PCB
PJ
PCB mismatching Any PCB of specification different from that of
the product is connected.
PCB of different specification
mounted
P4
Defective radiation fin thermistor The radiation fin thermistor gets short circuited
or open.
Defective radiation fin thermistor
CHECK 9

Содержание