Daikin FXSQ32P7VEB [282/370] Inverter radiation fin temperature rise abnormality

Daikin FXHQ100MAVS [282/370] Inverter radiation fin temperature rise abnormality
Troubleshooting by Indication on the Remote Controller SiBE311209
273 Service Diagnosis
4.42 Inverter Radiation Fin Temperature Rise Abnormality
Remote
Controller
Display
P4
Applicable
Models
Outdoor Unit: RTSQ8~16PAY1
Function Unit: BTSQ20PY1
Method of Error
Detection
Resistance of radiation fin thermistor is detected when the compressor is not operating.
Error Decision
Conditions
When the resistance value of thermistor becomes a value equivalent to open or short circuited
status
Error is not decided while the unit operation is continued.
"
P4
" will be displayed by pressing the inspection button.
Supposed
Causes
Defective inverter radiation fin thermistor
Defective inverter PCB
Defective inverter compressor
Defective fan motor
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
Replace the inverter
PCB.
Measure the resistance value
of the inverter radiation fin
thermistor.
Is the thermistor
resistance value
normal?
Disconnect the connector (X111A) from the
radiation fin thermistor, and then check the
thermistor.
The INV.
compressor's
insulation resistance
is not more than
100k.
The fan motor's
insulation resistance
is not more than
1M.
Does the error recur
when the power
supply turns ON?
YES
YES
NO
YES
YES
NO
NO
Replace the
compressor (M1C).
Replace the fan motor.
Replace the inverter
PCB.
Continue the operation.