SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 238
4.19 Outdoor Unit Fan Motor Abnormality
Remote
Controller
Display
E7
Applicable
Models
Outdoor Unit: RTSQ8~16PAY1
Method of Error
Detection
Detect an error based on the current value in the inverter PCB (as for motor 2, current value in
the fan PCB).
Detect an error for the fan motor circuit based on the number of rotation detected by hole IC
during the fan motor operation.
Error Decision
Conditions
Overcurrent is detected for inverter PCB (A4P) or fan inverter PCB (A5P)
(System down is caused by 4 times of detection.)
In the condition of fan motor rotation, the number of rotation is below the fixed number for
more than 6 seconds. (System down is caused by 4 times of detection.)
Supposed
Causes
Defective fan motor
Defect or connection error of the connectors/ harness between the fan motor and PCB
The fan can not rotate due to any foreign substances entangled.
Clear condition: Continue normal operation for 5 minutes