Troubleshooting by Indication on the Remote Controller SiBE311209
281 Service Diagnosis
4.47 Check Operation is not Executed
Remote
Controller
Display
U3
Applicable
Models
Outdoor Unit: RTSQ8~16PAY1
Method of Error
Detection
Check operation is executed or not executed
Error Decision
Conditions
Error is decided when the unit starts operation without check operation.
Supposed
Causes
Check operation is not executed.
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Has the check
operation performed
on outdoor unit
PCB?
NO
YES
Press and hold BS4 on the outdoor
master PCB for 5 seconds or more,
or turn ON the field setting mode 2-
3 to conduct a check operation.
Performs the check operation again
and completes the check operation.