Daikin FXSQ32P7VEB [115/370] Pump down residual operation in heating operation outdoor unit

Daikin FXZQ25MVE4 [115/370] Pump down residual operation in heating operation outdoor unit
SiBE311209 Special Control
Function 106
8.1.2 Pump down Residual Operation in Heating Operation (Outdoor Unit)
8.1.3 Function Unit [Only applicable to heating operation at low outdoor
air temperature]
Actuator
Electric
symbol
Master unit operation
Slave unit operation
(RTSYQ20PAY1 only)
Compressor 1 M1C 124 Hz
OFFCompressor 2 M2C OFF
Compressor 3 M3C OFF
Outdoor unit fan 1 M1F
Fan STEP No. 8 Fan STEP No. 4
Outdoor unit fan 2 M2F
Electronic expansion valve (Main) Y1E 0 pls 0 pls
Electronic expansion valve
(Subcooling)
Y3E 0 pls 0 pls
Electronic expansion valve
(Refrigerant charge)
Y2E 80 pls 80 pls
Solenoid valve (Refrigerant
regulator gas vent pipe)
Y1S OFF OFF
Four way valve (Heat exchanger
switch)
Y3S ON ON
Solenoid valve (Refrigerant
regulator liquid pipe )
Y4S OFF OFF
Solenoid valve (Hot gas) Y5S OFF OFF
Solenoid valve (Main bypass)
Y6S ON ON
Solenoid valve (Refrigerant
regulator discharge pipe)
Y7S OFF OFF
Solenoid valve (Refrigerant
regulator discharge pipe)
Y8S OFF OFF
Solenoid valve (Heat exchanger
hot gas)
Y9S OFF OFF
Four way valve (High/low pressure
gas pipe switch)
Y2S OFF OFF
Ending conditions
3 min.
Master unit Pe < 0.24 MPa
Master unit Pc > 3.14 MPa
Master unit Tdi > 110°C
Master unit Tp > 140°C
OR
Part name Electric symbol Function unit operation
Compressor M1C OFF
Electronic expansion valve (Liquid
injection)
Y1E 0 pls
Electronic expansion valve (Two-
stage switching-1)
Y2E1 0 pls
Electronic expansion valve (Two-
stage switching-2)
Y2E2 0 pls
Solenoid valve (Hot gas) Y1S OFF
Solenoid valve (Two-stage pressure
reducing)
Y2S OFF
Solenoid valve (Bypass 1) Y3S OFF ON (Pc > 2.45MPa)
Solenoid valve (Bypass 2) Y4S OFF ON (Pc > 2.45MPa)
Solenoid valve (Liquid line switch) Y5S OFF ON (after a lapse of 15 sec.)
Ending conditions A lapse of 30 sec.