SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 262
Troubleshooting
Refer to P.307.
1. List of Inverter PCBs
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Turn OFF the power supply
once, and then check the
compressor lead wires.
Do the lead wires have any
disconnection, broken wire,
short circuit, or ground
fault?
YES
NO
Turn ON the power supply
again.
Does the power
supply normally
restart?
YES
NO
While in monitor mode,
check the unit concerned.
Check if the
power transistor is
normal.
NO
YES
Check if the
power transistor of
the fan driver is
normal.
NO
YES
Check if insulation
resistance of the
compressor is 100k
and above.
NO
YES
Replace the lead wires.
It is supposed that the error results
from external causes other than
failures (e.g. exogenous noises or
thunder).
Replace the compressor and
compressor inverter PCB (A4P) at
the same time.
Replace the inverter PCB (A4P).
Replace the compressor inverter
PCB (A4P) and fan inverter PCB
(A5P).
Replace the inverter PCB (A4P).
CHECK 4
CHECK 4
Model Name Electric symbol
RTSQ 8, 10, 12PA
Compressor inverter PCB A4P
Fan inverter PCB A5P
RTSQ 14, 16PA
Compressor inverter PCB A4P
Fan inverter PCB A5P, A8P
BTSQ20P Compressor inverter PCB A3P
CHECK 4