Daikin FXSQ32P7VEB [273/370] Momentary overcurrent of inverter compressor

Daikin FXSQ80PVE [273/370] Momentary overcurrent of inverter compressor
SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 264
4.37 Momentary Overcurrent of Inverter Compressor
Remote
Controller
Display
L5
Applicable
Models
Outdoor Unit: RTSQ8~16PAY1
Method of Error
Detection
Error is detected from current flowing in the power transistor.
Error Decision
Conditions
When an excessive current flows in the power transistor
(Instantaneous overcurrent also causes activation)
Supposed
Causes
Defective compressor coil (disconnected, defective insulation)
Compressor startup error (mechanical lock)
Defective inverter PCB
Troubleshooting Compressor inspection
Refer to P.307.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
YES
Is the stop
valve is
open?
Are the
compressor
lead wires
normal?
Are the wiring
and connection to
the compressor
normal?
Insulation
resistance of the
compressor is
100 k or less.
Compressor coils
are disconnected.
CHECK 4
Is the power transistor
normal?
Error occurs again
after restarting the
unit.
Power OFF
NO
NO
NO
YES
NO
YES
NO
NO
YES
NO
YES
Open the stop valve.
Replace the compressor
lead wires.
Correct the wiring and
connection.
Replace the inverter
compressor.
Replace the inverter
compressor.
Replace the inverter
PCB (A4P).
Continue the
operation.
Momentary power
failure is possible.
Replace the inverter
compressor.
YES
YES
CHECK 4