Daikin FXSQ32P7VEB Сервис мануал онлайн [181/370] 544690

Daikin FXZQ50MVE4 Сервис мануал онлайн [181/370] 542853
SiBE311209 Field Setting
Test Operation 172
The numbers in the "No." column represent the number of times to press the
SET (BS2) button.
1: Number of connected indoor units
Used to make setting of the number of indoor units connected to an outdoor
unit.
2: Number of outdoor units
Used to make setting of the number of outdoor units connected to DIII-NET
that is one of the communication lines.
3: Number of terminal units
Used to make setting of the number of indoor units connected to DIII-NET
that is one of the communication lines.
(Only available for VRV indoor units)
No. Setting item
LED display
Data display
H1P H2P H3P H4P H5P H6P H7P
0 Various settings
lhhhhhh
Lower 4 digits
2 Low noise/demand address
lhhhhkh
Lower 6 digits
4 AIRNET address
lhhhkhh
5
Number of connected indoor units
1
lhhhkhk
7
Number of connected zone units
(Fixed to "0")
lhhhkkk
8 Number of outdoor units 3
lhhkhhh
11 Number of zone units
lhhkhkk
Lower 6 digits
12 Number of terminal units 5
lhhkkhh
Lower 4 digits:
upper
13 Number of terminal units 5
lhhkkhk
Lower 4 digits:
lower
14 Contents of error (the latest)
lhhkkkh
Error code table
Refer to
P.202~203
15 Contents of error (1 cycle before)
lhhkkkk
16 Contents of error (2 cycle before)
lhkhhhh
20 Contents of retry (the latest)
lhkhkhh
21 Contents of retry (1 cycle before)
lhkhkhk
22 Contents of retry (2 cycle before)
lhkhkkh
25 Number of multi-outdoor-unit
lhkkhhk
Lower 6 digits
c. Monitor mode
To enter the monitor mode, press the
MODE (BS1) button when in
“Setting mode 1”.
<Selection of setting item>
Press the SET (BS2) button and set
the LED display to a setting item.
<Confirmation on setting contents>
Press the RETURN (BS3) button to
display different data of set items.
Press the RETURN (BS3) button
and switches to the initial status of
“Monitor mode”.
Press the MODE (BS1) button and
returns to “Setting mode 1”.