102 1.8 External Control Adaptor for Outdoor Unit <DTA104A61 / DTA104A62 / DTA104A53>
Adaptor ED721208
Fig. 2 (Ex.) To set the outdoor unit’s COOL/HEAT address to No. 15 :
—Off —On —Flicker 5-bit
Procedure Setting contents MODE TEST
C/H SELECT
L.N.O.P.
SEQ.
START
IND
MASTER
SLAVE
When power turned on Setting mode (factory setting)
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Hold down next page button for
5 sec.
Enters address setting.
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Press operation button one time.
Enters COOL/HEAT address
setting. LED20 LED21 LED22 LED23 LED24 LED25 LED25
Press confirmation button one
time.
Make sure COOL/HEAT
address has been entered. LED20 LED21 LED22 LED23 LED24 LED25 LED25
Press operation button 15 times.
(Address No. = Times pushed)
Sets COOL/HEAT address.
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Press confirmation button two
times.
Check COOL/HEAT address.
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Press next page button one
time.
Returns to set mode.
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Fig. 3 (Ex.) To set the outdoor unit’s demand address to No. 7 :
—Off —On —Flicker 5-bit
Procedure Setting contents MODE TEST
C/H SELECT
L.N.O.P.
SEQ.
START
IND
MASTER
SLAVE
When power turned on Setting mode (factory setting)
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Hold down next page button for
5 sec.
Enters address setting.
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Press operation button two
times.
Enters demand address setting.
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Press confirmation button one
time.
Make sure demand address has
been entered. LED20 LED21 LED22 LED23 LED24 LED25 LED25
Press operation button 7 times.
(Address No. = Times pressed)
Sets demand address.
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Press confirmation button two
times.
Check demand address.
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Press next page button one
time.
Returns to set mode.
LED20 LED21 LED22 LED23 LED24 LED25 LED25
Fig. 1
: OFF : ON
C/H
LOWER
ADRESS
CENTRAL
NO.
DEMAND CONTROL ADRESS
Setting of 5-bit COOL/
HEAT address by DS1,2
Designate and set COOL/
HEAT addresses 0-31 for
each operation mode switch
unit.
No. 0
No. 7
No. 8
No. 15
No. 16
No. 31
Upper 2
bits DS2
Lower 3
bits DS1