2.3 Connection Method 19
ED721208 Fundamental of DIII-NET
2
2.3.2 Incorrect Wiring Example
Caution:
Communication problems could occur.
[Incorrect Wiring 1]
Series wiring method only should be used.
Caution:
As shown above, the centralized control equipment should be connected to the wiring between the outdoor units,
wherever possible. (If connected to the control wiring between indoor unit and the outdoor unit, it may not be able to
control the units even on the normal circuit if the circuit connected to the centralized control equipment is out of order.)
Centralized
Control
Equipment