Daikin RXYQ120PYDN [37/405] Setting group address for centralized control 33

Daikin RCXYQ20MAY1 [37/405] Setting group address for centralized control 33
5.2 Setting Group Address for Centralized Control 33
ED721208 Fundamental of DIII-NET
2
5.2.5 Heat Reclaim Ventilator Wired Remote Controller <BRC301B61>
The following shows the procedure how to set the group address for the centralized control equipment by the remote controller for
Heat Reclaim Ventilator.
Purpose
When you use the
centralized
control equipment
, you have to
set the each unit connected to
the DIII-NET line.
Controller
z BRC1C62
z BRC301B61
Operating procedure
Press the INSPECTION button for more than
four seconds.
Use the VENTILATION MODE, AIRFLOW
RATE to select the mode No. “00”.
Use the top or lower section of the TIMER
button to set the group address for the
centralized control equipment.
Press the PROGRAM / CANCEL button to
enter the setting group address shown on the
display.
Press INSPECTION button to return to normal
mode.
Note:
Do not duplicate the group address.
Be sure to supply the power to the remote controller side.
(It cannot be set without the power supply.)
BRC301B61
UNIT No.
FRESH UP
CODE
GROUP
A
A
hr
hr
SETTING
(1)
(Auto-address setting)
(4)
(3)
(2)
(5)
(1)(7)
(4)(5)
(3)
(3)
(2)
(4)
(5)
(6)
FIELD
SETTING
MODE
Set the group address of each group of the Heat
Reclaim Ventilator from the remote controller. (In
case of no remote controller, also connect the remote
controller and set the group address. Then, remove
the remote controller.)
(1) Turn ON the power of the indoor unit and
centralized control equipment. (Unless the power
is ON, no setting can be made.)
(Group address increase in the order of 1-00,
1-01,···1-15, 2-00, ···8-15.)
GROUP
ADDRESS
Check that the installation and electrical wiring
are correct before turning the power supply ON.
(When the power supply is turned ON, all LCD
appear once and the unit may not accept the
operation for about one minute with the
display of "
88".)
(2) While in the normal mode, press the " "
button for a minimum of 4 seconds.
The remote controller will enter the FIELD
SETTING MODE.
(3) Select the MODE No. "
00" with the " "button.
(4) Use the " " button to select the group address
for each group.
(5) Press " " to set the selected group address.
(6) Press " " to return to the NORMAL MODE.