Daikin RXYQ120PYDN [61/405] Input a

Daikin RXYQ24PHY1 [61/405] Input a
1.1 Wiring Adaptor for Electrical Appendices (1) <KRP2A61 / KRP2A62 / KRP2A53> 57
ED721208 Adaptor
4
2. Setting control mode selector switch (RS1)
Using control mode selector switch (RS1), select the control mode as described below.
(1) When operating with only individual display function
(2) When operating with constant input from A
Note:
Input B is for forced-OFF. When ON, stop + remote controller is rejected, and input A is ignored. When OFF, even if A
is ON, the contents of when input A is ON, are not achieved. Input A must therefore be re-input.
(3) When operating with momentary input from A
(Use a momentary input of ON time 200 msec or longer.)
For demand control from input B
Forced thermostat OFF command
Forces indoor unit to operate the fan only.
Forced temperature shift command
The indoor unit operates at 2°C higher (cooling) or 2°C lower (heating) than the set temperature.
Note:
In zone control, operation is displayed as long as one indoor unit is running. When in the last command priority mode,
some units are not operating while ON.
In such case, even if input A is ON, the unit and all other units in the same zone will stop.
Position Function
0 Individual Display (Input Ignored)
CONTROL
MODE
Position
Function
Input A ON Input A OFF Input B ON
Operation
or not of
indoor
unit
From Remote
controller
Operation
or not of
indoor
unit
From Remote
controller
Operation or not
of indoor unit
From
Remote
Controller
1
Remote Control
Rejection
ON Rejection
OFF Rejection Forced OFF
Rejection
2 Central Priority ON Acceptable
3
Stop by Remote
controller Acceptable
ON
Only Stop
acceptable
4
Remote controller
acceptance / rejection
Permit Acceptable
Position Function
Input A ON Constant Input B ON (Input A is ignored)
Operation or
not of indoor
unit
From Remote controller
Operation or
not of indoor
unit
From Remote controller
5 Remote Control Rejection ON/OFF Rejection
Forced OFF Rejection
6 Last command Priority ON/OFF Acceptable
Position Function when input A is ON Function when input B is ON
C
Remote controller rejected (Same as position “5”)
Forced thermostat OFF command
D Forced temperature shift command
E
Last command priority (Same as position “6”)
Forced thermostat OFF command
F Forced temperature shift command
RS1
RS1
1
Input A
Input B
B1
B2
BC