Daikin RXYQ120PYDN [349/405] Ed721208 commissioning manual
![Daikin RQCEQ848P [349/405] Ed721208 commissioning manual](/views2/1708729/page349/bg15d.png)
345
ED721208 Commissioning Manual
6
17 Commissioning Manual (External Management Points) EM11A026
DCM601A51 intelligent Touch Manager
%58ƂNGHQTOCV
6JGHQTOCVQHVJG%58HKNGQWVRWVHTQOVJGK6/KUCUUJQYPDGNQY#%58HKNGQWVRWVYJGPPQ
OCPCIGOGPVRQKPVFCVCKUTGIKUVGTGFECPDGWUGFCUCVGORNCVGHQTPGYKORNGOGPVCVKQPUUKPEG
QPN[VJGCTGCWUGFD[VJGU[UVGOCPFVJGJGCFGTRQTVKQPCTGQWVRWV
6JGHQNNQYKPIVCDNGUJQYUVJG%58HQTOCVHQTOCPCIGOGPVRQKPVFCVCTGIKUVTCVKQP
r 0WOGTKEXCNWGUKPFKECVGFKPGCEJKVGOEQTTGURQPFVQVJGEQNWOPPWODGTKPVJG%58ƂNGVJGƂTUVEQNWOPKU
ƂZGFCPFWUGFHQTFCVCV[RGKFGPVKƂECVKQP$NCPMKVGOUKPFKECVGVJGTGKUPQCRRNKECDNGFCVC
%NCUUKƂECVKQP
-G[YQTF &GUETKRVKQP 8CNWG
/CPCIGOGPVRQKPVV[RG
'ZVGTPCN
#K
'ZVGTPCN
&K
'ZVGTPCN
&KQ
Common
— *GCFGTV[RGKFGPVKƂECVKQP —
':6'40#.
#+*
':6'40#.
&+*
':6'40#.
&+1*
— &CVCV[RGKFGPVKƂECVKQP —
':6'40#.
#+&
':6'40#.
&+&
':6'40#.
&+1&
21+06+& /CPCIGOGPVRQKPV+& 101 to 1000000 2
0#/' 0COG
5VTKPIVQEJCTCEVGTUTGICTFNGUUQHUKPINGQT
FQWDNGD[VG
3
&'6#+.'&+0(1 &GVCKNGFKPHQTOCVKQP
5VTKPIVQEJCTCEVGTUTGICTFNGUUQHUKPINGQT
FQWDNGD[VG
4
241*+$+612 2TQJKDKVOCPWCNQRGTCVKQP #NNQYGF2TQJKDKVGF 5
214601 2QTVPWODGT
&+PVGTPCN2K/CKPWPKVVQ
'ZVGTPCNVQ
556
#&&4'55
7RRGTNGXGNCFFTGUU
ITQWR
&VQ
'ZVGTPCNVQ
+PVGTPCN2KVQ
1WVFQQTWPKVVQ
/CKPWPKVVQVQHQT2QTV
6
#&&4'55
.QYGTNGXGNCFFTGUU
WPKV
&&KQ&&K+PFQQTWPKV8GPVKNCVQT%JKNNGTVQ
56#465612/10 105VCVWU/QPKVQT
'ZVGTPCN&KVQ
'ZVGTPCN&KQ105VCVWU/QPKVQTCFFTGUUVQ
0QVURGEKƂGF
67
014/#.#$014/#./10
0QTOCN#DPQTOCN/QPKVQT
0QTOCN#DPQTOCN/QPKVQT+PRWVCFFTGUUVQ
0QVURGEKƂGF
78
56#465612 101((QRGTCVKQP #NYC[U+PUVCPV 9
56#465612#&&4 5VCTV5VQRCFFTGUU
#NYC[UVQ
+PUVCPV10CFFTGUUVQ
10
56#465612#&&4 5VCTV5VQRCFFTGUU
#NYC[U*CPFNGFCUKPXCNKF
+PUVCPV1((CFFTGUUVQ
11
+%10 +EQP+& 100 to 999 7 8 12
#0#&&4 #%055#FFTGUU +PFQQTWPKVVQ+PXCNKF
/QPKVQTKPI
%1//10.8
%QOOWPKECVKQPGTTQT
OQPKVQTKPINGXGN
/QPKVQTKPI/QPKVQT*KUVQT[ 8913
Содержание
- Air conditioners 1
- E e d e n 1 3 7 2 1 2 0 8 1
- I n t e l l i g e n t to u c h m a n a g e r 1
- Technical data 1
- Revision history 2
- Centralized control equipments which can use with intelligent touch manager 4 7 appendix 5 3
- Contents 3
- Design of diii net 6 3
- Diii net design standard 7 3
- Group and zone 9 3
- Part 1 intelligent touch manager 1 3
- Part 2 fundamental of diii net 15 3
- Part 3 power proportional distribution ppd 37 3
- Ppd design guide 8 3
- Reference material 7 3
- Table of contents 3
- Unit and group 6 4 number of connectable units 7 3
- Adaptor for air conditioning system 2 4
- Adaptor for other equipment 08 4
- Intelligent touch manager 06 2 itm layout screen creation tool 12 3 itm external management points 29 4 itm power proportional distribution setup 47 5 itm energy navigator setup 386 4
- Part 4 adaptor 51 4
- Part 5 installation manual 133 4
- Part 6 commissioning manual 205 4
- Safety precautions 34 2 intelligent touch manager 36 3 itm plus adaptor 73 4 itm integrator 92 4
- Part 1 intelligent touch manager 5
- Appendix 35 19
- Centralized control equipments which can use with intelligent touch manager 34 19
- Design of diii net 16 19
- Diii net design standard 17 19
- Group and zone 29 19
- Number of connectable units 27 19
- Part 2 fundamental of diii net 19
- Unit and group 26 19
- Design of diii net 20
- Features of diii net 20
- Detail of outdoor unit terminal no 21
- Diii net design standard 21
- Just for operation with each remote controller 21
- Outdoor unit 21
- Terminal number 21
- Connection method 22
- Correct wiring 22
- Incorrect wiring example 23
- Conflict 25
- Wiring this part is prohibited 25
- 2 wiring example 26
- Caution 26
- Example of control wiring be sure to connect the wiring of the centralized control equipment to control wiring between outdoor units when wiring connections are made between indoor and outdoor units there may be cases where control over normal systems may become impossible if one of the connected systems should happen to fail be sure to prevent the connection of three wires on the same terminal 26
- Fundamental of diii net ed721208 26
- It is not recommended to connect the centralized control equipment on α 1 α 2 α 3 as there is a risk to loose control over all systems ex if intelligent touch manager itm is connected on α 1 and system1 shut down control over system2 and system3 units is lost 26
- The advantages when the centralized control equipment are connected to a if the centralized control equipment are connected to a it is still possible to have a centralized control even if the power supply of other circuit connected to the centralized control equipment is shut off even if the power is shut off due to long vacation etc 26
- When all the centralized control equipment is located at one place 26
- Wiring example 26
- Caution 27
- Ed721208 fundamental of diii net 27
- It is not recommended to connect the centralized control equipment on α 1 α 2 α 3 as there is a risk to loose control over all systems ex if intelligent touch manager itm is connected on α 1 and system1 shut down control over system2 and system3 units is lost 27
- The advantages when the centralized control equipment are connected to a if the centralized control equipment are connected to a it is still possible to have a centralized control even if the power supply of other circuit connected to the centralized control equipment is shut off even if the power is shut off due to long vacation etc 27
- When the centralized control equipment are located at several places 27
- Wiring example 23 27
- Recommendation of installation diii net expander adaptor 28
- Wiring length 28
- Wiring specifications of diii net 28
- Fundamental of diii net ed721208 30
- I u indoor unit o u outdoor unit r c remote controller 30
- Indoor unit and r c no of group no of indoor unit 30
- Outdoor unit no of outdoor unit 30
- Unit and group 30
- Each module is counted as 1 unit 31
- Number of connectable units 31
- Number of units to be connected vrv supplementary explanation 31
- Chiller chiller 32
- Connection of devices other than vrv 32
- Ed721208 fundamental of diii net 33
- Group address 33
- Group address 29 33
- Group and zone 33
- Set a group address to a device to be connected to diii net the range of addresses to be set is 64 types as shown below 33
- You cannot set a same group address on a same diii net you do not need to set a group address to a child unit in a remote control group in case power proportional distribution is used you need to set a group address to a child unit in a remote control group as well 33
- Setting group address for centralized control 34
- Ed721208 fundamental of diii net 37
- Setting group address for centralized control 33 37
- Centralized control equipments which can use with intelligent touch manager 38
- Following centralized control equipments can connect to the same diii net with an intelligent touch manager 38
- Fundamental of diii net ed721208 38
- Appendix 39
- Ed721208 fundamental of diii net 39
- Error code on initial setting and wiring troubles 39
- Under centralized control 39
- Under centralized control 35 39
- Part 3 power proportional distribution ppd 41
- Ppd design guide 38 41
- Reference material 47 41
- Confirmation of watthour meter 42
- Ppd design guide 42
- System architecture 42
- Calculation condition 43
- Design precautions 43
- Setting of each electric power group 44
- Caution it is possible to register to the same electric power group for the following combination 1 vrv vrvii heat pump r 22 r 407c 2 vrv heat recovery r 22 r 407c 3 vrvii vrviii heat pump r 410a 4 vrvii vrviii heat recovery r 410a when the combination of the above mentioned is not observed a correct power proportional distribution calculation cannot be done 45
- Design precautions 41 45
- Ed721208 power proportional distribution ppd 45
- For heat recovery outdoor units the watthour meter must be independently installed 1 for heat recovery there is a case that the power consumption is less than vrv and vrv plus 2 however if different systems are put on the one meter the electric power distribution would be calculated by constant counting and the calculation result would then more than the actual value on all indoor units 45
- Not allowed with 1 unit 45
- The reason why vrv heat recovery must not be included 45
- Therefore it is necessary to install the watthour meter independently as shown in fig 2 in addition the power port no in address table must be different from others to be set at test operation 45
- Explanations of power proportional distribution 46
- Since this system detects power consumption as the base of billing specified watthour meters should be used by all means 46
- What is the power proportional distribution ppd 46
- Fxfq80p 2 power consumption at no operation 50 2 25w 47
- Rxyq5p crankcase heater s output 50w 47
- Count accuracy 48
- Bev unit 50
- Outdoor unit 50
- Super wiring diii net 50
- Reference material 51
- Set a group address to b d g and h for ppd this setting can be configured in the field setting no 30 by remote controller the setting method is described in page 332 slave indoor units can not be displayed on the screen of itm if they are removed from registration at a management point because itm cannot control the slave indoor units even if slave indoor units are not displayed on the itm screen electric power can be distributed to the indoor units as long as the group addresses are registered with a power group at ppd setup 52
- In the following case power consumption of the outdoor unit is allocated to indoor unit h 53
- There is no particular remedy take measures such as setting a schedule to turn off units 53
- Adaptor for air conditioning system 52 55
- Adaptor for other equipment 108 55
- Part 4 adaptor 55
- Adaptor ed721208 56
- Adaptor for air conditioning system 56
- Ex zone control for 8 units of fxfq63pve control groups of 4 3 and 1 56
- Function 56
- Note 1 individual indoor units connected to the centralized line cannot be displayed individually on the bms 56
- The krp2a61 62 53 enables operation by remote control on off control temperature setting operation display error display with it the following system can be built note however that the adaptor cannot be used with other centralized control equipment 56
- This system requires the following parts wiring adaptor for electrical appendices 1 krp2a61 or krp2a62 or krp2a53 remote controller switches for control 56
- Zone control this adaptor is connected to the centralized line and all the air conditioners connected to the central control lines f1 f2 are under unified control unified control of a max 64 groups of a max 16 indoor units each but the max indoor units are 128 56
- Fxk q fxc q 57
- Installation 57
- Part names and functions 57
- Fxl q fxn q 58
- Fxm q 200 250 58
- Fxm20 140 58
- Fxmq20 140p 58
- Fxs fxsyq fxyb 58
- Fxyd ka 58
- Wiring to the adaptor 59
- Adaptor ed721208 60
- For non voltage input 60
- For voltage input 60
- Remote control input operation control 60
- Wire as described below wiring differs depending on whether using a voltage or non voltage input 60
- Input a 61
- Input b 61
- Setting control mode selector switch rs1 61
- 4 when operating with dual momentary inputs from a and b use a momentary input of 200 msec or longer 62
- Adaptor ed721208 62
- Note doing constant input a with position 7 a it will be forced off function input a is ignored constant input cannot use for input b with position b 62
- Central priority 63
- Input a 63
- Input b 63
- Krp2a61 63
- Operation by 63
- Position 7 63
- Position 8 63
- Position 9 63
- Position a 63
- Remote controller acceptance rejection 63
- Remote controller rejection 63
- Stop by remote controller acceptable 63
- Timing chart for each control mode by pulse input 63
- Adaptor ed721208 64
- Indoor unit pcb 64
- Mm² length max 70 m important keep transmission wiring at least 50 mm away from power supply wiring to avoid malfunctions 64
- Note wiring resistance included in above figures 64
- Temperature setting corresponds to resistance values in the range of 0 to 135 ω their relationship is as shown below 64
- Temperature setting input 64
- Wiring specifications wiring sheathed wire gauge 1 64
- Output display signals 65
- Adaptor ed721208 66
- Function 66
- Note 1 marked shows wiring adaptor for electrical appendices 2 marked indicates the same control range 3 the wiring adaptor for electrical appendices 2 can control simultaneously the group of the units max 16 units connected to the remote control wiring line p1 p2 in another words all the units connected between p1 and p2 terminal have the same control 66
- Note 1 this adaptor cannot be used together with centralized control equipment 2 the model of adaptor differs according to the type of indoor unit to be installed 66
- This adaptor is an interface required to connect the indoor unit with the bas and by installing this adaptor in the indoor unit it enables you to have various remote controls on off temperature setting operation status display and malfunction display one adaptor can control simultaneously the group of units max 16 units connected to the remote control wiring line p1 p2 66
- Applied model 67
- Ed721208 adaptor 67
- Note 1 fh nu fdbg nu fdbt nu and fdmg pu are not connected 2 installation box for adaptor pcb is necessary 67
- Note 1 this is valid only for the indoor unit which has a temperature setting function 2 terminal no x18a is for the indoor unit of vrv system for skyair series and other air conditioner connect to the relevant terminal for each units 67
- Part names and functions 67
- Fcq n k a 68
- Fh y k 68
- Fhq fh y 68
- Fx y c 68
- Fxzq ffq 68
- Installation 68
- Ceiling mounted built in type 69
- Ceiling mounted built in type ceiling suspended cassette type 69
- Ceiling mounted duct type 69
- Ed721208 adaptor 69
- Fbq d a 69
- Fh y b 69
- Fxm40 125 69
- Fxmq20 140p 69
- Fxs fxyb 69
- Note installation box is necessary for second adaptor fxs 69
- Faq100bvv1b fa y f a 70
- Faq71bvv1b fay l 70
- Fxl q fxn q 70
- Fxyd ka 70
- Electric wiring work and initial setting 71
- Adaptor ed721208 72
- Central priority on acceptable 72
- Control mode position rs1 function 72
- From remote controller 72
- From remote controller operation or not of indoor unit from remote controller 72
- Input a close input a open input b close input a is ignored 72
- Input a close open pulse input constant input b close constant input input a is ignored 72
- Input ignored 72
- Note the value of resistance includes the resistance of wiring the setting temperature is limited within the setting range of indoor unit if you set the temperature outside of the range by the adaptor it controls at the nearest setting range 72
- Off rejection forced off 72
- Operation or not of indoor unit 72
- Position function 72
- Rejection 72
- Relation between the setting temperature and the resistance are as follows 72
- Remote control rejection on off rejection forced off at close rejection 6 last command priority on off acceptable 72
- Remote control rejection on rejection 72
- Remote controller acceptable rejection on only stop acceptable 72
- Remote controller acceptance rejection off permit acceptable 72
- Setting of control mode selector switch rs1 72
- Temperature setting corresponds to resistance values in the range of 0 to 135 ω their relationship is as shown below 72
- Temperature setting input 72
- A the system is shut down forcibly ignored input a constant input cannot be used for input b at position b 2 refer to the followings for the outline of above functions 73
- Description of functions outline 73
- Ed721208 adaptor 73
- Note 1 when constant input is used for input b at position 73
- Central priority 74
- Close close input a 74
- Close close open 74
- Close input a 74
- Close open 74
- Input a 74
- Input a input b 74
- Input b 74
- Last command priority 74
- Operation by krp4aa51 74
- Remote controller acceptance rejection 74
- Remote controller off acceptable 74
- Remote controller rejection 74
- Timing chart for each control mode by momentary input 74
- Precautions before use for the wiring adaptor for electrical appendices 2 75
- Adaptor ed721208 76
- And bms 76
- Applicable skyair indoor unit fh y k fj fh y c k fhc d fh y b f fvy la fa y f a fxuq m a fuy fj 76
- Function 76
- Note 1 fcq n k and fbq d are equipped standardly with the interface adaptor and this option is unnecessary 2 this adaptor is not connected with fh nu fdbg nu fdbt nu fdmg nu and fdmg pu 76
- Note 1 it is limited when connecting interface for bacne 76
- Part names and functions 76
- This adaptor enables the following operation and monitor function from centralized control equipment 76
- This interface adaptor is necessary when connecting to skyair indoor unit to centralized control equipment central remote controller unified on off controller schedule timer etc by connecting centralized control equipment unified operation on off timer operation remote controller rejection acceptance setting and operation error monitor etc are possible 76
- Accessories check if the following accessories are included in the kit 77
- Ed721208 adaptor 77
- Installation 77
- Adaptor ed721208 80
- And bms 80
- Applicable skyair indoor unit ffq b fhq bv faq bv fbq b note fcq n k and fbq d are equipped standardly with the interface adaptor and this option is unnecessary 80
- Electric wiring work 80
- Function 80
- Note 1 it is limited when connecting interface for bacne 80
- This adaptor enables the following operation and monitor function from centralized control equipment 80
- This interface adaptor is necessary when connecting to skyair indoor unit to centralized control equipment central remote controller unified on off controller schedule timer etc by connecting centralized control equipment unified operation on off timer operation remote controller rejection acceptance setting and operation error monitor etc are possible 80
- Wire this kit as described below make sure wires to units do not pass over the pcb when wiring 80
- Ed721208 adaptor 81
- Installation and electric wiring 81
- Function 82
- Components 83
- Ed721208 adaptor 83
- Installation 83
- Part names 83
- Adaptor ed721208 84
- All wiring components and materials to be procured on site must comply with the applicable local and national codes use copper conductors only all field wiring and components must be provided by licensed electrician unit shall be grounded in compliance with the applicable local and national codes after wiring work check power to the equipment shuts off when swich is shut off 84
- Changel the connection of transformer according to the right table especially for y1 model 84
- Clamp these wires by clamp materials certainly clamp the earth wire see right fig do not clamp the high voltage wires field wires and the low voltage wiers lead wire and thermistor both inside and outside of the control board box 84
- Connect the field wires to the air conditioner details see the back side ground the control board box 84
- Connect the read wires of centralized control equipment see the below fig ground the sheild of the cords to the control board box 84
- Connect the read wires of remote controller see the below fig ground the sheild of the cords to the control board box 84
- Electric wiring work 84
- Finished wiring situation 84
- General instructions 84
- Use the wire shown right for between the unit and the control board box connect the wiring between indoor and outdoor units centralized control equipment and remote controller for details refer to the installation manual of them remove the cover of the control board box after setting it parts situation is shown right fig install the thermistor throgh the bush it is in the control board box see below fig 84
- Warning 84
- Wiring specification 84
- Connect between the air conditioner and dta107a55 shown below 85
- Connect the wiring between the box of this kit and the el compo box assy of the air conditioner refer to the wiring diagram of the air conditioner 85
- Connect the wiring between the box of this kit and the el compo box assy of the indoor unit refer to the wiring diagram of the indoor unit 85
- Connection of the terminal 85
- Ed721208 adaptor 85
- In case of fd03 05k 85
- In case of fd06 10k 85
- In case of fd15 20k 85
- In case of uat06 10k uat06 12ka 85
- In case of uat15 20k uat15 21ka 85
- In case of uaty06k 85
- See below for connecting the terminal m3 the output of alarm signal about these models we can only output the alarm signal of indoor fan motor connect the wiring between the terminal m3 and the terminal 96 of magnetic contactor of indoor fan motor k1m 85
- See below for connecting the terminal m3 the output of alarm signal connect the wiring between the terminal m1 and the terminal 6 of k3r magnetic relay connect the wiring between the terminal m3 and the terminal 4 of k3r magnetic relay 85
- See below for connecting the terminal m3 the output of alarm signal connect the wiring between the terminal m1 and the terminal 6 of k4r magnetic relay connect the wiring between the terminal m3 and the terminal 4 of k4r magnetic relay 85
- See below for connecting the terminal m3 the output of alarm signal in case of y1 connect the wiring between the terminal m1 and the terminal 5 of k2r magnetic relay connect the wiring between the terminal m3 and the terminal 3 of k2r magnetic relay in case of y19 connect the wiring between the terminal m3 and the terminal 8 of k4r magnetic relay in case of tal and yal use the attached wire harness and change from the wire to it the wire is connected between k1r 6 k1r 7 k2r 7 and k3r 6 is shown the terminal connect the wiring between the terminal m3 and the solderless splices butt m3 of the wire assy 85
- See below for connecting the terminal m3 the output of alarm signal use the attached wire harness and change from the wire to it the wire is connected between k1r 5 k1r 7 k2r 7 and k3r 5 is shown the terminal connect the wiring between the terminal m3 and the solderless splices butt m3 of the wire assy 85
- See below for connecting the terminal m3 the output of alarm signal use the attached wire harness and change from the wire to it the wire is connected between k1r 5 k1r 7 k2r 7 and k3r 6 is shown the terminal connect the wiring between the terminal m3 and the solderless splices butt m3 of the wire assy 85
- Adaptor ed721208 86
- Connect the wiring between the box of this kit and the el compo box assy of the air conditioner refer to the wiring diagram of the air conditioner 86
- Field setting 86
- In case of uaty08 12k 86
- In case of uaty15 21k 86
- See below for connecting the terminal m3 the output of alarm signal in case of y1 connect the wiring between the terminal m1 and the terminal 5 of k2r magnetic relay connect the wiring between the terminal m3 and the terminal 3 of k2r magnetic relay in case of y19 connect the wiring between the terminal m3 and the terminal 8 of k4r magnetic relay in case of tal and yal use the attached wire harness and change from the wire to it the wire is connected between k1r 5 k1r 7 k2r 7 and k3r 5 is shown the terminal connect the wiring between the terminal m3 and the solderless splices butt m3 of the wire assy 86
- See below for connecting the terminal m3 the output of alarm signal in case of y1 connect the wiring between the terminal m1 and the terminal 6 of k2r magnetic relay connect the wiring between the terminal m3 and the terminal 4 of k2r magnetic relay in case of y19 connect the wiring between the terminal m3 and the terminal 8 of k4r magnetic relay in case of tal and yal connect the wiring between the terminal m1 and the terminal 6 of k14r magnetic relay connect the wiring between the terminal m3 and the terminal 4 of k14r magnetic relay 86
- Functions 87
- Adaptor ed721208 88
- Electric wiring work and initial settings 88
- Forced stop settings switch sw3 1 88
- Lower group number switch sw1 upper group number switch sw2 1to 3 88
- Part names and functions 88
- Power supply terminal s8 connect an external dc 12v power supply only when reading the operating error display 88
- Service monitor led1 green when the cpu is working properly the led flashes 88
- 2 group number settings sw1 and sw2 1 to sw2 3 set these when using the centralized control equipment set to the side do not set more than one unit to the same number 89
- 3 settings when recovering from a power outage sw2 4 this selects whether to restart operation when the power comes back on after a power outage occurred during operation this setting is given priority in cases where the indoor unit has an auto start on off jumper note also that regardless of whether switch sw2 4 is on or off the operating mode set temperature fan direction and speed settings and remote control prohibition status are stored 89
- 4 contact input function settings sw3 1 to sw3 2 when using contact input s1 choose one of the following functions 89
- Automatic operation is not available from the centralized control equipment when using automatic operation using the wireless remote controller the centralized control equipment displays automatic cooling heating and 25 c even if the temperature is changed it will return to 25 c after a while 89
- Constant contact input 89
- Destination sw3 3 setting what happens 89
- Ed721208 adaptor 89
- However these settings do not need to be made when using the schedule timer independently the settings are needed when used in conjunction with another dcs series centralized control equipment in this case the schedule timer performs an auto address after the power is turned on so new group numbers are automatically set settings made using the switches will be overwritten 89
- Instantaneous contact input factory setting 89
- Note 1 since centralized control equipment and ha jem a compatible equipment both use last command priority the contact status and operating status of the air conditioner might not match sometimes example if the unit is run from the centralized control equipment while the air conditioner is stopped with an open contact the contact will be open and the unit will be running 2 operating mode and fan direction and speed settings can be changed 89
- Note also that a separate timer power supply is needed when using the schedule timer independently power supply specs dc 16v 10 15 200ma recommended power supply omron s82j 01015a should be used with the output voltage adjusted to the center dc 16v 89
- Off factory setting 89
- Off off 89
- On automatic operation is available from the centralized control equipment 89
- On invalid 89
- Open the kit s case and set the switches on the circuit board 1 for overseas japanese unit setting sw3 3 room air conditioners different methods are used for setting the temperature in automatic mode so this switch needs to be set 89
- Stops after recovering from a power outage off factory setting 89
- Stops if the unit was stopped before the power outage and runs if it was running 89
- Sw2 4 setting what happens 89
- Turn the power on after all the switches have been set settings made while the power is on are invalid 89
- What happens control mode s1 operating mode sw3 2 setting sw3 1 setting 89
- Adaptor ed721208 90
- Bms field supply 90
- Forced stop 90
- Krp928b2s 90
- Last command priority 90
- On off control is rejected 90
- Only off control is accepted 90
- Permitted 90
- Prohibited 90
- Relay specs mr1 and mr2 coil voltage dc 12v coil resistance 160 ω 10 matsushita electric hc relay omron my relay wiring length max 100m 90
- S8 power supply for relay dc 12v 90
- The operating error signals can be read from the contact output s5 output specs m1 turn mr 1 on when the air conditioner is running m2 turn mr 2 when a communication error has occurred between the krp928b2s and the air conditioner or mr 1 is on and the unit has stopped after an error mr 2 is not turned on during a warning 90
- The remote controller permission prohibition settings using the intelligent touch controller are as follows permitted prohibited 90
- When using the centralized control equipment the operating codes can be used to limit operation from wireless remote controllers permitted prohibited 90
- Functions 91
- Krp1b61 krp1ba54 b56 ba57 ba59 91
- Krp1c63 krp1c64 91
- Part name 91
- Accessories 92
- Installation 92
- Fxl q fxn q 93
- Fxm q 200 250 93
- Fxm40 125 93
- Fxyd ka 93
- Accessories 94
- Fhq fxh q 94
- Fcq n kvea fxfq pve 95
- Adaptor ed721208 96
- Electric wiring work 96
- Fan on display 96
- Fetching the operation display signal attaching an hour meter 96
- If optional accessories are installed auxiliary electric heater humidifier wire correctly in accordance with the attached installation manual refer to the wiring diagram applied to the indoor unit when running electric wiring 96
- Krp1b61 96
- Refer to the wiring diagram attached to the indoor unit before attempting to wire make sure wires to units do not pass over the pcb when wiring wire the adaptor to the indoor unit as shown below 96
- Fxzq fxd q x16a 97
- Indoor unit pcb 97
- Function 99
- Accessories 100
- Adaptor ed721208 100
- Check the following accessories are included in the kit before the installation 100
- External control adaptor for outdoor unit pcb support 4 100
- Installation 100
- Installation manual 100
- Part name and functions 100
- The installation box for adaptor pcb are required with the following air conditioner models 100
- The kit type dta104a61 type dta104a62 type dta104a53 type varies according to air conditioner model 100
- This adaptor is not applicable to the outdoor unit with anti corrosion treatment models e 100
- 600 ceiling mounted cassette type ceiling mounted duct type 101
- B s v q 101
- Bs unit ceiling mounted cassette type 101
- Ceiling mounted cassette type ceiling mounted built in type 101
- Ed721208 adaptor 101
- Adaptor ed721208 102
- Ceiling mounted cassette type ceiling suspended type 102
- Ceiling mounted duct type 102
- Fxm40 125 102
- Fxmq20 140p 102
- Note installation box for adaptor pcb is required to install the adaptor 102
- See part of krp4a96 in option handbook oh12 01 102
- Wall mounted type floor standing type concealed floor standing type 102
- Electric wiring work and initial setting 103
- The contents of the various settings for unified switching of the operation mode cool heat fan are as follows 104
- Adaptor ed721208 106
- Installation point 107
- Adaptor ed721208 108
- Function 108
- With the adaptor 108
- Without the adaptor 108
- Accessories 109
- Adaptor 109
- Check the following accessories are included in the kit before the installation 109
- Installation 109
- Part name and functions 109
- This adaptor does not apply to salt damege resistsnce 109
- Electric wiring work 110
- System with more than 10 outdoor units 111
- Wiring restrictions see electric wiring work apply to each group a and b 111
- Adaptor ed721208 112
- Adaptor for other equipment 112
- Function 112
- Installation 112
- Note install the adaptor inside a control box of outer dimensions 230w 230d 60h supply a control box at site with outer dimensions equal to or larger than those shown below 230w 230d 60h 112
- Part names and functions 112
- Securely install the adaptor with the attached installation screw 112
- This kit contains an i o interface adaptor for centralized control equipment used when there is a non connectable air conditioner and electrical equipment when connected to the centralized control equipment this adaptor enables operation stop and display of operation error monitors from the centralized control equipment 112
- Electric wiring work 113
- Ed721208 adaptor 115
- Hz 220 240v source and a 115
- Hz 220v source check power supply specifications and properly wire the source to the adaptor 115
- Make settings before turning on the power 115
- Note ground wires as shown in the figure on the above the adaptor may malfunction or be damaged if improperly wired the fuse is designed for short circuit protection overcurrent protection therefore it may not offer sufficient protection against improper voltage 115
- Note group number need not be set on this adaptor during individual use with either a wiring adaptor for electrical appendices or a schedule timer setting is automatic ex setting group no 1 15 first and second group no s are indicated as below 115
- Power supply can be selected from a 115
- Rs1 switch setting and upper group no position 115
- Rs2 switch setting and lower group no position 115
- Set the group no at the centralized control group no setting switches rs1 and rs2 refer to the below table to set group no group no increases in the order of 1 00 1 01 1 15 2 00 4 15 refer to the installation manual of the centralized control equipment 115
- Adaptor ed721208 116
- Function 116
- Operating and error input 116
- Unit dec101a51 116
- Using this unit connection of other facilities other than air conditioner is made possible such as power supply facility sanitary facility anti disaster facility and crime prevention facility 116
- When the contact is open or closed error is produced for changeover refer to 2 initial setting input specifications no voltage a contact the welding current is approx 10ma when the applied voltage is 20 to 30vdc and the contact is closed for input use the contact for micro current 12vdc 1ma max 116
- Part names and functions 117
- Abnormal input detecting switch ds2 ds3 118
- Adaptor ed721208 118
- Ambient humidity 95 rh or less no condensation 118
- Applied standard safety standard iec730 emc standard cispr22 a emi cispr24 ems 118
- Contact information on off abnormality is transmitted to intelligent touch controller intelligent manager iii through diii net communication 118
- Di board 118
- Environment for storage outdoor air temperature 20 to 60 c 118
- Environment for use outdoor air temperature 15 to 60 c 118
- Error detecting switch ds6 2 118
- For the power supply use 1 200 240v 118
- Input contacts 118
- Installation method indoor installation 118
- It is possible to select whether the equipment connection error is a non latch or latch error 118
- It is possible to select whether the error at startup is masked for 10 or 30 seconds 118
- Micro computer ok monitor led a green 118
- Monitor input switch ds6 3 118
- Points 8 pairs based on a pair of on off input and abnormality input 118
- Power supply terminal block l n 118
- Power supply to be supplied from outside 118
- Quantity change shortcircuit pin tp1 118
- Rating ac200 240v 50 60hz 118
- Set diii net address no 118
- Shortcircuit during control quantity setting 118
- Specifications 118
- Start error mask switch ds6 1 118
- Switch for selecting the number of facility equipment connected ds4 ds5 118
- The figure below shows the printed circuit board built in this equipment 118
- The power transformer connector is connected 118
- Transformer connecting connector cn1 cn2 118
- Transmission error monitor led10 red 118
- When the transmission is abnormal the lamp lights up disabling remote control the lamp goes out in the normal condition 118
- Installation 119
- Electric wiring work and initial setting 121
- For wiring connection remove the front panel secured with 2 screws of this equipment upon completion of operation given in this paragraph and 2 initial setting below close the front panel with the screws described above 121
- Since malfunctioning may result also in case where the wirings described above are routed in parallel be sure to connect the wirings at least 50 mm apart from the other 121
- Wiring lead in 121
- Adaptor ed721208 122
- Ds2 abnormal input detection open close concentrated address 4 to 7 abnormal input detection method 122
- Ds3 abnormal input detection open close concentrated address 0 to 3 open close 122
- Ds4 buzzer output on off concentrated address 4 to 7 on off switching of buzzer output of buzzer unit upon detection of failure 122
- Ds5 buzzer output on off concentrated address 0 to 3 on off 122
- Ds6 1 startup failure masking time after detecting operation input 10 seconds 30 seconds 122
- Ds6 2 failure detection recovery method upon detection of failure automatic reset retained 122
- Ds6 3 monitor input detection of failure under halting status yes no 122
- Initial setting dec101a51 switch settings 122
- Name operation off on 122
- Note all are set to off upon shipment from factory 122
- On off 122
- Open close 122
- Set address no low order with the centralized address setting switch rs1 referring to the table below set the address number low order address nos are 1 00 1 01 1 15 2 00 4 15 122
- Set the top address of this equipment with the diii net setting switch ds1 rs1 using the diii net setting switch ds1 set the range of address no that is set in this equipment address nos 1 00 to 1 15 are factory controlled before shipment 122
- Ds2 ds3 setting this switch selects whether the input is abnormal with the abnormal input contact a1 to a8 open or closed off factory preset before shipment abnormal in the open condition on abnormal in the closed condition the relationship between each switch and abnormal input is as described below input a1 ds2 3 1 input a2 ds2 3 2 input a3 ds2 3 3 input a4 ds2 3 4 input a5 ds2 3 5 input a6 ds2 3 6 input a7 ds2 3 7 input a8 ds2 3 8 123
- Ds4 ds5 123
- Ed721208 adaptor 123
- Shortcircuit with power on 123
- This equipment can use the addresses between 1 00 and 4 15 it is impossible to use address 5 00 and subsequent addresses and use any address in duplication example when the top address was set to 4 14 the number of facility equipment cannot be set to 8 in this case set it to 1 or 2 123
- Tp1 setting facility equipment quantity change this function is used to set the number of facility equipment controllable with this equipment the number of controllable facility equipment factory shipment is 8 setting method 1 turn the power on with tp1 short circuited and change the quantity of facility equipment according to the ds4 5 setting the relation between ds4 5 setting and facility equipment quantity is as per the table below 2 turn the power off 3 open the tp1 and turn all ds4 5 switches off 4 turn the power on again 5 short circuit the tp1 and check to see if the setting coincides with the number of facility equipment connected to this equipment 6 finally open the tp1 123
- Unit 2 units 123
- Adaptor ed721208 124
- After checking the power supply specifications make correct connections connect the earth wiring to the terminal use a 2 m 124
- Connect the power supply and earth see the power supply earth wiring paragraph 124
- Electric wiring connection 124
- For power supply 1 200 240 v is used the wiring to the power terminal block l n is required the electric wire used should be 1 5 to 2 m 124
- For the wiring connection and clamping method refer to the wiring lead in paragraph 124
- Power supply earth wiring 124
- The connection to the facility equipment and setting of various switches are required see the wiring with facility equipment paragraph 124
- The length of wiring between this equipment and facility equipment is 100m max 124
- Wiring between this equipment and centralized control equipment is required 124
- Wiring procedure 124
- Wiring with facility equipment 124
- Dio unit dec102a51 125
- Ed721208 adaptor 125
- Function 125
- Using this unit connection of other facilities other than air conditioner is made possible such as power supply facility sanitary facility anti disaster facility and crime prevention facility 125
- Adaptor ed721208 126
- Operation output it is possible to select continuous 1 output 4 points or instantaneous 2 output on off pair 2 points for switching refer to 2 initial setting 126
- Wiring at continuous output up to 4 facility equipments can be connected 126
- Wiring at instantaneous output up to 2 facility equipments can be connected 126
- Abnormal input when the contact is open or closed error is produced for changeover refer to 1 electric wiring work and initial setting input specifications no voltage a contact the welding current is approx 10ma when the applied voltage is 20 to 30v dc and the contact is closed for input use the contact for micro current 12v dc 1ma max 127
- After checking the power supply specifications make correct connections connect the earth wiring to the terminal use a 2 m 127
- Ed721208 adaptor 127
- For power supply 1 200 240v is used the wiring to the power terminal block l n is required the electric wire used should be 1 5 to 2 m 127
- Operation input 127
- Power supply earth wiring 127
- Terminal used in case where the switch was set to continuous output con or instantaneous output ins 127
- When the contact is closed run is to be inputted input spec no voltage a contact when the applied voltage is 20 to 30v dc and the contact is closed the welding current is approx 10ma for input use a contact for micro current 12v dc 1ma max 127
- When the switch was set to ins instantaneous output the operation input terminals m3 m4 and abnormal input terminals a3 a4 are not used 127
- Part names and functions 128
- Ed721208 adaptor 129
- The figure below shows the pc board built in this equipment 129
- Adaptor ed721208 130
- Input specs voltage free a contact micro current load contact input dc12v 1 ma or less wiring length 150 m 130
- Output specs voltage free a contact 130
- Specifications 130
- Installation 131
- Restrictions in continuous installation 132
- Electric wiring work and initial setting 133
- Since malfunctioning may result also in case where the wirings described above are routed in parallel be sure to connect the wirings at least 50mm apart from the other 133
- To 1 200 240v and earth to facility equipment to facility equipment to terminals f1 f2 of the centralized control equipment or terminals f1 f2 of other equipment outdoor unit dec101a51 102a51 133
- Adaptor ed721208 134
- Ds2 setting 135
- Ds4 1 setting this switch selects the control output status after power failure occurred in this equipment and the power was recovered off factory preset before shipment the control power after power recovery is handled as stop output on the control output after power recovery is handled as output before power failure 135
- Ed721208 adaptor 135
- Example 1 when the top address was set to 1 00 and the number of facility equipment was set to 2 it follows that 1 00 and 1 01 are being used example 2 when the top address was set to 3 15 and the number of facility equipment was set to 4 it follows that 3 15 4 00 4 01 and 4 02 are being used 135
- In this case it follows that this equipment uses address nos 1 08 to 1 11 4 numbers max 135
- Number of centralized addresses used the number of centralized addresses used is determined by the top address set in this paragraph and the number of facility equipment connected that is set in tp1 setting facility equipment quantity change paragraph 135
- Set address no low order with the centralized address setting switch rs1 referring to the table below set the address number low order address nos are 1 00 1 01 1 15 2 00 4 15 135
- Set the top address of this equipment with the diii net setting switch ds1 rs1 135
- This equipment can use the addresses between 1 00 and 4 15 it is impossible to use address 5 00 and subsequent addresses and use any address in duplication example when the top address was set to 4 14 the number of facility equipment cannot be set to 4 in this case set it to 1 or 2 135
- This switch selects whether the input is abnormal with the abnormal input contact a1 to a4 open or closed off factory preset before shipment abnormal in the open condition on abnormal in the closed condition the relationship between each switch and abnormal input is as described below input a1 ds2 1 input a2 ds2 2 input a3 ds2 3 input a4 ds2 4 135
- Using the diii net setting switch ds1 set the range of address no that is set in this equipment address nos 1 00 to 1 15 are factory controlled before shipment 135
- Wiring procedure 136
- Wiring with facility equipment 136
- Part 5 installation manual 137
- Caution 138
- Safety precautions 138
- Warning 138
- Caution 139
- Warning 139
- Before installation 7 140
- Connection 14 140
- Contents 140
- Installation 25 140
- Installation manual ed721208 140
- Intelligent touch manager 140
- Ed721208 installation manual 141
- Before installation 142
- Checking that all accessories are included 142
- Installation manual ed721208 142
- Ed721208 installation manual 143
- Installation manual 3p291714 1 dcm601a51 intelligent touch manager english 143
- Intelligent touch manager body 143
- Wall mounting metal plate 143
- Angle bracket 144
- English 144
- Frame bracket 144
- Installation manual 3p291714 1 dcm601a51 intelligent touch manager 144
- Installation manual ed721208 144
- Ed721208 installation manual 145
- Rear face 145
- Installation manual ed721208 146
- Ed721208 installation manual 147
- Routing of cables 147
- Side face 147
- Installation manual ed721208 148
- Connection 149
- Ed721208 installation manual 149
- Installation manual ed721208 150
- Ed721208 installation manual 151
- Connecting a lan cable 152
- Installation manual ed721208 152
- Ed721208 installation manual 153
- Installation manual ed721208 154
- Ed721208 installation manual 155
- Installation manual ed721208 156
- Ed721208 installation manual 157
- Installation manual ed721208 158
- Ed721208 installation manual 159
- Installation 160
- Installation manual ed721208 160
- Parts to be used 160
- Ed721208 installation manual 161
- Parts to be used 161
- Installation manual ed721208 162
- Ed721208 installation manual 163
- Installation manual ed721208 164
- Ed721208 installation manual 165
- Parts to be used 165
- Installation manual ed721208 166
- Ed721208 installation manual 167
- Installation manual ed721208 168
- Ed721208 installation manual 169
- Assigning a diii net address for each air conditioner 170
- Installation manual ed721208 170
- Ed721208 installation manual 171
- Installation manual ed721208 172
- Ed721208 installation manual 173
- Installation manual ed721208 174
- Ed721208 installation manual 175
- Installation manual ed721208 176
- Procedure 176
- Before installation 7 177
- Connection 12 177
- Contents 177
- Installation 22 177
- Itm plus adaptor 177
- Before installation 178
- Checking that all accessories are included 178
- Installation manual ed721208 178
- Ed721208 installation manual 179
- Front face of itm plus adaptor 179
- Installation manual ed721208 180
- Ed721208 installation manual 181
- Required space 181
- Installation manual ed721208 182
- Connection 183
- Ed721208 installation manual 183
- Connecting intelligent touch manager 184
- Installation manual ed721208 184
- Ed721208 installation manual 185
- Installation manual ed721208 186
- Ed721208 installation manual 187
- Installation manual ed721208 188
- Ed721208 installation manual 189
- Installation manual ed721208 190
- Ed721208 installation manual 191
- Installation manual ed721208 192
- Installation 193
- Installation manual ed721208 194
- Installation procedure 194
- Ed721208 installation manual 195
- Before installation 7 196
- Connection 14 196
- Contents 196
- Installation manual ed721208 196
- Itm integrator 196
- Before installation 197
- Checking that all accessories are included 197
- Ed721208 installation manual 197
- Installation manual 3p291714 5 dcm601a53 itm integrator english 198
- Installation manual ed721208 198
- Itm integrator body 198
- Wall mounting metal plate 198
- Angle bracket 199
- Ed721208 installation manual 199
- English 199
- Frame bracket 199
- Installation manual 3p291714 5 dcm601a53 itm integrator 199
- Installation manual ed721208 200
- Rear face 200
- Ed721208 installation manual 201
- Installation manual ed721208 202
- Routing of cables 202
- Side face 202
- Ed721208 installation manual 203
- Connection 204
- Installation manual ed721208 204
- Connecting a lan cable 205
- Ed721208 installation manual 205
- Installation manual ed721208 206
- Ed721208 installation manual 207
- Installation manual ed721208 208
- Part 6 commissioning manual 209
- About the itm intelligent touch manager 210
- Basic functions 3 210
- Contents 210
- Detailed screen description 210
- Engineering 210
- Intelligent touch manager 210
- Names and functions 210
- Service settings 3 210
- System overview 210
- Ed721208 commissioning manual 211
- Itm integrator 09 211
- Itm integrator explanation 09 211
- Operating optional functions 7 211
- Optional functions 4 211
- Service settings 4 211
- System settings 7 211
- Appendix 20 212
- Useful information 20 212
- About the itm intelligent touch manager 213
- System overview 213
- At the site 214
- Carried out on site after installation 214
- Commissioning manual ed721208 214
- Engineering 214
- New installation without using the pre engineering tool 214
- Various engineering works are necessary for using the itm 214
- At the site 215
- Ed721208 commissioning manual 215
- New installation by using the pre engineering tool 215
- 2 logging into service mode 216
- Commissioning manual ed721208 216
- 1 setup screen structure 218
- Basic functions 218
- Detailed screen description 218
- Names and functions 218
- 2 service settings tab 219
- Ed721208 commissioning manual 219
- Commissioning manual ed721208 220
- 3 system settings tab 221
- Ed721208 commissioning manual 221
- 1 mgmt point data regist 222
- Basic functions 222
- Commissioning manual ed721208 222
- Service settings 222
- Ed721208 commissioning manual 223
- Registering a management point with the itm unit 223
- Commissioning manual ed721208 224
- Ed721208 commissioning manual 225
- Commissioning manual ed721208 226
- Ed721208 commissioning manual 227
- Check items list 228
- Check results on the information check screen 228
- Checking the setting results 228
- Commissioning manual ed721208 228
- If an error is found discards the edited content retained until then and restores the saved original data 228
- No error is displayed if no error is found touch the close button to close the screen 228
- Touching the check button 13 checks the content of the current settings data and displays the 228
- Ed721208 commissioning manual 229
- Commissioning manual ed721208 230
- Common 1 tab 230
- Detailed mgmt point attributes screen and button descriptions 230
- Displayed items vary depending on the management point type 230
- Management point type set up by switching the displayed tabs as necessary 230
- Sets common items for a management point 230
- Tabs and items displayed on the mng point attributes screen vary depending on the selected 230
- The following describes the mng point attributes screen in detail 230
- 15 port no address combo box 231
- Appears 231
- Duplicated addresses cannot be registered all addresses must be different 231
- Ed721208 commissioning manual 231
- For the address select it using the combo box 231
- For the port number touch the modify button and enter it in the numerical input dialog that 231
- Sets up the port number and address to which the management point belongs 231
- 16 detailed type 232
- 17 mgmt pt id 232
- 18 name 232
- 19 detailed info 232
- 20 icon 232
- Commissioning manual ed721208 232
- Displays the detailed management point type however you cannot modify it here 232
- Displays the management point id automatically allocated by the system however you cannot 232
- Double byte 232
- Modify it here 232
- Set up information about the management point as necessary 232
- Sets up the icon for the management point 232
- Sets up the management point name 232
- Specify a name for the management point using 1 to 12 characters irrespective of single or 232
- The number of characters you can enter is 0 to 50 irrespective of single or double byte 232
- Touch the modify button and enter the name in the name input dialog that appears 232
- Touch the modify button and enter the value in the text input dialog that appears 232
- Touch the modify button and set the icon in the icon setup screen that appears 232
- Ed721208 commissioning manual 233
- Commissioning manual ed721208 234
- Ed721208 commissioning manual 235
- Commissioning manual ed721208 236
- Ed721208 commissioning manual 237
- Commissioning manual ed721208 238
- Ed721208 commissioning manual 239
- Acceptable range for each numeric value 240
- Commissioning manual ed721208 240
- Ed721208 commissioning manual 241
- Commissioning manual ed721208 242
- Ed721208 commissioning manual 243
- Commissioning manual ed721208 244
- Commissioning manual em11a021 dcm601a51 intelligent touch manager 36 245
- Ed721208 commissioning manual 245
- Management point data is registered can be used as a template for new implementations since 245
- Only the area used by the system and the header portion are output 245
- The following table shows the csv format for management point data registration 245
- Commissioning manual ed721208 246
- Commissioning manual em11a021 dcm601a51 intelligent touch manager 37 246
- 2 other setting 247
- Ed721208 commissioning manual 247
- 3 diii net engineering 248
- Commissioning manual ed721208 248
- 3 is a list of connector plugs for each itm port 4 is a list of central units recognized on the 249
- Ed721208 commissioning manual 249
- If you install or uninstall another controller please review the configuration of the setpoint 249
- Port selected in 3 249
- Pressing the refresh button 5 updates 3 and 4 touching the ok button displays a 249
- Range limit 249
- That can be installed together are as follows 249
- This itm is not displayed in 4 249
- 4 time zone 250
- 5 changeover option 250
- Commissioning manual ed721208 250
- 1 is an air conditioner list displaying all group addresses when no management points are 251
- 2 comm err group address of the connected unit with communication error 251
- Changeover option for the other indoor units in the same refrigeration system also becomes 251
- Ed721208 commissioning manual 251
- Maintenance a group address of a connected unit under maintenance 251
- Registered columns other than group addr are displayed blank 251
- Screen using the close button 251
- Select the indoor unit for which you want to release the changeover option from 1 and touch 251
- Select the indoor unit for which you want to set the changeover option from 1 and touch the 251
- Selectable touching the refresh button 4 updates the contents displayed in 1 close the 251
- Settings button 2 the changeover option becomes able at that moment the changeover 251
- The displayed contents are as indicated in the table below 251
- The release button 3 the changeover option becomes selectable at that moment the 251
- 6 history mgmt delete 252
- Commissioning manual ed721208 252
- 7 pre engineering 253
- Ed721208 commissioning manual 253
- Commissioning manual ed721208 254
- Relationship between the assumed scenario and functions 254
- Displaying the main screen 255
- Download the pre engineering tool from the distributor s page 255
- Ed721208 commissioning manual 255
- Indicated in the table below 255
- Pc requirement for running the pre engineering tool 255
- Start up the pre engineering tool on the pc 255
- To use the pre engineering tool a separate pc is necessary the requirements for the pc are as 255
- Commissioning manual ed721208 256
- Main screen 256
- Ed721208 commissioning manual 257
- Scenario 1 installation to new property 257
- Commissioning manual ed721208 258
- Screen of demo version for pc 258
- Ed721208 commissioning manual 259
- Commissioning manual ed721208 260
- Ed721208 commissioning manual 261
- Commissioning manual ed721208 262
- Ed721208 commissioning manual 263
- Scenario 3 restore with existing property s backup data 263
- 8 upgrade 264
- Commissioning manual ed721208 264
- Scenario 4 implementation of new functions due to existing property s upgrade 264
- 9 backup 265
- Ed721208 commissioning manual 265
- Commissioning manual ed721208 266
- 10 installation 267
- Ed721208 commissioning manual 267
- Commissioning manual ed721208 268
- 11 contact info 269
- Ed721208 commissioning manual 269
- 12 setting outdoor unit 271
- Caution 271
- Ed721208 commissioning manual 271
- Commissioning manual ed721208 272
- Commissioning manual em11a021 dcm601a51 intelligent touch manager 63 272
- In the application using the diii net expander adapter if you monitor the outdoor units or 272
- Intended functions monitoring of outdoor units energy navigator and leakage detection 272
- Jumper pins were cut and those directly connected to itm should be 10 or less 272
- Need to cut the jumper pin of the diii net expander adapter 272
- Precautions when using diii net expander adapter 272
- Table of types 272
- The jumper pin to be cut is j1 only 272
- The total number of outdoor units connected to the diii net expander adapter whose j1 272
- There are two jumper pins to be cut so be sure to cut both of 272
- Use internal pi or such other functions processed based on information from the outdoor units you 272
- Commissioning manual em11a021 dcm601a51 intelligent touch manager 64 273
- Ed721208 commissioning manual 273
- Commissioning manual ed721208 274
- Commissioning manual em11a021 dcm601a51 intelligent touch manager 65 274
- Commissioning manual em11a021 dcm601a51 intelligent touch manager 66 275
- Ed721208 commissioning manual 275
- Commissioning manual ed721208 276
- Commissioning manual em11a021 dcm601a51 intelligent touch manager 67 276
- Commissioning manual em11a021 dcm601a51 intelligent touch manager 68 277
- Ed721208 commissioning manual 277
- 1 activation 278
- Acquiring the activation key 278
- Entering the activation key 278
- Optional functions 278
- Service settings 278
- Ed721208 commissioning manual 279
- 2 dealer option setup 280
- Commissioning manual ed721208 280
- 1 network 281
- Operating optional functions 281
- System settings 281
- Commissioning manual ed721208 282
- Ed721208 commissioning manual 283
- 2 web remote management 284
- Commissioning manual ed721208 284
- For settings necessary on the itm unit see 6 1 network this chapter describes the pc setup 284
- Procedure 284
- Such as a web browser the requirements for the pc are as indicated in the table below 284
- The itm can be remotely operated via the internet or local network 284
- To use the web remote management functions you need to separately prepare a pc and software 284
- And itm unit by referring to the connection diagrams below 285
- Connect the pc and itm unit into a network using an ethernet cable 285
- Connecting the pc and itm 285
- Ed721208 commissioning manual 285
- Ethernet cables use for connecting networks come in two types straight and cross connect the pc 285
- Straight cable connection diagram cross cable connection diagram 285
- Use a 100base tx or higher ethernet cross cable 285
- Use a 100base tx or higher ethernet straight cable 285
- When connecting the pc and itm directly 285
- When connecting the pc and itm via a hub 285
- Checking the web browser and flash player versions 286
- Commissioning manual ed721208 286
- Ed721208 commissioning manual 287
- Setting up the ip address windows xp professional 287
- Administrator and set them up 290
- Commissioning manual ed721208 290
- Ip address 192 68 subnet mask 255 55 55 290
- Itm settings at shipment are as follows 290
- Properties and local area connection properties screens 290
- Set them up as follows when connecting to the itm via local network 290
- To connect to the itm via the internet ask its ip address and subnet mask to your network 290
- Ed721208 commissioning manual 291
- Setting up the ip address windows vista business 291
- Commissioning manual ed721208 294
- Ed721208 commissioning manual 295
- Setting up the ip address windows 7 professional 295
- Commissioning manual ed721208 298
- Precautions when using internet explorer on windows vista and windows 7 298
- Carry out the following procedure from the pc 299
- Check whether the ethernet connection between a pc and itm is normal 299
- Ed721208 commissioning manual 299
- Network connection check 299
- Commissioning manual ed721208 300
- Commissioning manual ed721208 302
- Logging into service mode via web remote management 302
- 1 basic setup 303
- Itm integrator 303
- Itm integrator explanation 303
- Commissioning manual ed721208 304
- Ed721208 commissioning manual 305
- Commissioning manual ed721208 306
- Ed721208 commissioning manual 307
- 2 itm integrator service settings 308
- Commissioning manual ed721208 308
- Commissioning manual em11a021 dcm601a51 intelligent touch manager 114 308
- Service settings described in this chapter are for the itm integrator unit settings for itm units are 308
- Set up the itm integrator unit 308
- The respective itm 308
- To be made in the respective itm or from the itm integrator standard view screen by accessing 308
- Ed721208 commissioning manual 309
- Service settings tab menu list screen 309
- Commissioning manual ed721208 310
- Controller access setup 310
- Ed721208 commissioning manual 311
- Commissioning manual ed721208 312
- Ed721208 commissioning manual 313
- 1 troubleshooting 314
- Appendix 314
- Commissioning manual ed721208 314
- Useful information 314
- Commissioning manual em11a021 dcm601a51 intelligent touch manager 121 315
- Ed721208 commissioning manual 315
- Commissioning manual ed721208 316
- Contents 316
- Itm layout screen creation tool 316
- Layout screen creation tool 316
- Available with the layout screen functionality dealer option allows you to create layout screens in 317
- Creation tool 317
- Description of the tool set see the appropriate pages of the commissioning manual 317
- Ed721208 commissioning manual 317
- Layout screen creation tool 317
- See the following table for the hardware and software requirements to run the layout screen 317
- You need a separate pc to run the layout screen creation tool 317
- Click the four corners of the window in the ascending order of the numbers indicated on the 318
- Commissioning manual ed721208 318
- Enter daikin as the password and then click the ok button to bring up the following dialog box 318
- Launching the layout screen creation tool 318
- Main screen 318
- Use the following procedures to work with the layout screen creation tool 318
- Which contains the edit layout screen button 318
- Ed721208 commissioning manual 319
- Alternatively you can point to a certain part on the display pane 4 and then click the right mouse 320
- Are editing the screen in the operation pane 3 the display pane 4 provides a preview of how the 320
- Button or press the appropriate key to perform your desired action 320
- Commissioning manual ed721208 320
- Management points by left clicking the appropriate buttons in the operation pane 3 320
- Mouse and keyboard actions 320
- Screen will be displayed on itm you can interact with the display pane 4 in the same way as when 320
- The edit screen window is divided into the operation pane 3 and the display pane 4 while you 320
- The following table provides a list of available mouse and keyboard actions 320
- To edit the layout screen you can perform actions such as adding deleting or moving areas or 320
- You are working within itm for more information see the user s manual em11a015 em11a017 320
- Ed721208 commissioning manual 321
- Setting up the screen 321
- Commissioning manual ed721208 322
- Ed721208 commissioning manual 323
- By using the screen change list setting you can limit the screen change for example changing 324
- Changable screens 324
- Commissioning manual ed721208 324
- Example 324
- In the example above changing to the screen d is possible only from the screen a 324
- Make the setting of changable screens according to the customer demand 324
- Only the screens shown in the list 324
- Screen a 324
- Screen b 324
- Screen c 324
- Screen d 324
- You need to make the screen change list setting for each screen 324
- Adding and editing areas or management points 325
- Ed721208 commissioning manual 325
- Commissioning manual ed721208 326
- Ed721208 commissioning manual 327
- Commissioning manual ed721208 328
- Ed721208 commissioning manual 329
- Exporting the screen data output 329
- Commissioning manual ed721208 330
- Ed721208 commissioning manual 331
- Commissioning manual ed721208 332
- Importing the layout screen data 332
- Contents 333
- External management points 333
- Itm external management points 333
- Commissioning manual ed721208 334
- External management points 334
- Maximum number of contacts per node 334
- Maximum number of points per external i o system 334
- Ed721208 commissioning manual 335
- Commissioning manual ed721208 336
- Management point mapping 336
- Ed721208 commissioning manual 337
- Supported i o modules 337
- Commissioning manual ed721208 338
- Connection with itm 338
- Ed721208 commissioning manual 339
- Modules that do not require a 24 v dc 339
- Power supply 339
- Precautions for connecting modules to itm 339
- Commissioning manual ed721208 340
- Registering external management points 340
- Ed721208 commissioning manual 341
- Commissioning manual ed721208 342
- Ed721208 commissioning manual 343
- Commissioning manual ed721208 344
- Ed721208 commissioning manual 345
- Commissioning manual ed721208 346
- Ed721208 commissioning manual 347
- 24 analog type 348
- 25 unit type 348
- 26 minimum value maximum value 348
- Commissioning manual ed721208 348
- Commissioning manual external management points em11a026 dcm601a51 intelligent touch manager 16 348
- Ed721208 commissioning manual 349
- Commissioning manual ed721208 350
- Commissioning manual external management points em11a026 dcm601a51 intelligent touch manager 18 350
- Commissioning for power proportional distribution 351
- Contents 351
- Itm power proportional distribution setup 351
- Commissioning for power proportional distribution 352
- Commissioning manual ed721208 352
- Precautions to take before commissioning 352
- Preparation for commissioning 352
- Ed721208 commissioning manual 353
- Commissioning manual ed721208 354
- Groups 354
- Ed721208 commissioning manual 355
- Commissioning manual ed721208 356
- Ed721208 commissioning manual 357
- Commissioning manual ed721208 358
- Commissioning manual ppd em11a027 dcm601a51 intelligent touch manager 8 358
- Commissioning manual ed721208 360
- Ed721208 commissioning manual 361
- Commissioning manual ed721208 362
- Ed721208 commissioning manual 363
- Commissioning manual ed721208 364
- Ed721208 commissioning manual 365
- Commissioning manual ed721208 366
- Ed721208 commissioning manual 367
- Commissioning manual ed721208 368
- Ed721208 commissioning manual 369
- Commissioning manual ed721208 370
- Ed721208 commissioning manual 371
- Commissioning manual ed721208 372
- Ed721208 commissioning manual 373
- Commissioning manual ed721208 374
- Ed721208 commissioning manual 375
- Commissioning manual ed721208 376
- Ed721208 commissioning manual 377
- Commissioning manual ed721208 378
- Ed721208 commissioning manual 379
- Commissioning manual ed721208 380
- Ed721208 commissioning manual 381
- Commissioning manual ed721208 382
- Ed721208 commissioning manual 383
- Commissioning manual ed721208 384
- Ed721208 commissioning manual 385
- Temporary power consumptio 385
- 43 update 44 386
- Commissioning manual ed721208 386
- Automatic distribution 387
- Calc type 387
- Calculating state 387
- Ed721208 commissioning manual 387
- Heater 387
- Save setup 45 387
- Commissioning manual ed721208 388
- Ed721208 commissioning manual 389
- Commissioning manual ed721208 390
- Contents 390
- Energy navigator setup 390
- Itm energy navigator setup 390
- Ed721208 commissioning manual 391
- Energy navigator setup 391
- Commissioning manual ed721208 392
- Commissioning manual energy navigator setup em11a028 dcm601a51 intelligent touch manager 4 393
- Ed721208 commissioning manual 393
- Commissioning manual ed721208 394
- Commissioning manual energy navigator setup em11a028 dcm601a51 intelligent touch manager 394
- Ed721208 commissioning manual 395
- Log into the service mode 396
- Commissioning manual ed721208 398
- Detailed view screen operational state 398
- Ed721208 commissioning manual 399
- Commissioning manual ed721208 400
- Ed721208 commissioning manual 401
- Commissioning manual ed721208 402
- Data clear 402
- 12 fs k 404
- Ask a qualified installer or contractor to install this product do not try to install the product yourself improper installation can result in water or refrigerant leakage electrical shock fire or explosion 404
- Cautions on product corrosion 404
- Daikin products are manufactured for export to numerous countries throughout the world prior to purchase please confirm with your local authorised importer distributor and or retailer whether this product conforms to the applicable standards and is suitable for use in the region where the product will be used this statement does not purport to exclude restrict or modify the application of any local legislation 404
- Ed721208 404
- If you have any enquiries please contact your local importer distributor and or retailer 404
- Read the user s manual carefully before using this product the user s manual provides important safety instructions and warnings be sure to follow these instructions and warnings 404
- Use only those parts and accessories supplied or specified by daikin ask a qualified installer or contractor to install those parts and accessories use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage electrical shock fire or explosion 404
- Daikin products are distributed by 405
- Eeden13 721208 10 12 copyright daikin printed on non chlorinated paper prepared by goekint graphics nv belgium responsible editor daikin europe n v zandvoordestraat 300 b 8400 oostende 405
- Naamloze vennootschap zandvoordestraat 300 b 8400 oostende belgium www daikin eu be 0412 120 336 rpr oostende 405
Похожие устройства
- Daikin RXYQ120PYDN Руководство по вводу в эксплуатацию
- Daikin RXYQ120PYDN Инструкция по эксплуатации
- Daikin RXYQ120PYDN Сервис мануал
- Daikin RXYQ120PTJU Сервис мануал
- Daikin RXYQ72PATJ Спецификация
- Daikin RXYQ72PATJ Руководство по вводу в эксплуатацию
- Daikin RXYQ96PATJ Спецификация
- Daikin RXYQ96PATJ Руководство по вводу в эксплуатацию
- Daikin RXYQ108PATJ Спецификация
- Daikin RXYQ108PATJ Руководство по вводу в эксплуатацию
- Sinbo SBG 7102A User guide
- Daikin RXYQ72PATJ Инструкция по монтажу
- Daikin RXYQ72PATJ Инструкция по эксплуатации
- Daikin RXYQ96PATJ Инструкция по монтажу
- Daikin RXYQ96PATJ Инструкция по эксплуатации
- Daikin RXYQ108PATJ Инструкция по монтажу
- Daikin RXYQ108PATJ Инструкция по эксплуатации
- Daikin RXYQ72PAYD Спецификация
- Daikin RXYQ72PAYD Руководство по вводу в эксплуатацию
- Daikin RXYQ96PAYD Спецификация