Daikin RXYQ120PYDN [73/405] A the system is shut down forcibly ignored input a constant input cannot be used for input b at position b 2 refer to the followings for the outline of above functions

Daikin RXYQ10MAY19 [73/405] A the system is shut down forcibly ignored input a constant input cannot be used for input b at position b 2 refer to the followings for the outline of above functions
1.2 Wiring Adaptor for Electrical Appendices (2) <KRP4AA51 / KRP4AA52 / KRP4AA53 / KRP4A54> 69
ED721208 Adaptor
4
Note:
1. When constant input is used for input B at position 7
~
A, the system is shut-down forcibly (Ignored input A). Constant
input cannot be used for input B at position B.
2. Refer to the followings for the outline of above functions.
Description of Functions (Outline)
Position Function
Input A close/open
(pulse input)
Input B close/open (pulse input)
Operation
or not of
indoor
unit
From Remote controller
Operation or not of
indoor unit
From Remote
controller
7 Remote Control Rejection ON Rejection
OFF at close Rejection
8 Last command Priority ON Acceptable
9
Remote controller OFF
Acceptable
ON Only Stop acceptable
A
Remote controller acceptance /
rejection, OFF
permit Acceptable
B Last command Priority ON Acceptable OFF Acceptable
C
Position 5 + Energy Saving
Control
The same as position 5
Forced thermostat OFF at ON
D
Position 5 + Temperature Set-
Back
Setting temperature shift command at ON
E
Position 6 + Energy Saving
Control
The same as position 6
Forced thermostat OFF at ON
F
Position 6 + Temperature Set-
Back
Setting temperature shift command at ON
1. Remote Control Rejection................................
For when you want to turn ON/OFF only by central remote controller. (ON/OFF
cannot be controlled by remote controller for indoor unit.)
2. Remote controller OFF Only Accepted ............
For when you want to turn ON only by the central remote controller, and turn OFF
only by remote controller for indoor unit.
3. Central Priority .................................................
For when you want to turn ON only by the central remote controller, and during
the set time, turn ON/OFF freely by remote controller for indoor unit.
4. Individual Priority (Last command priority) .......
For when you want to turn ON/OFF by both central remote controller and remote
controller for indoor unit.
5. Remote Controller Permission Timer ..............
For when you want to turn ON/OFF by remote controller for indoor unit during set
time, and you want to start the operation by remote controller for indoor unit at the
programmed time of system start.