32 5.2 Setting Group Address for Centralized Control
Fundamental of DIII-NET ED721208
5.2.4 Simplified Remote Controller <BRC2C51>
Procedure
1. Remove the upper part of remote controller.
2. When in the normal mode, press the BUTTON (field set), and the FIELD SET MODE is entered.
3. Select the desired MODE No. with the BUTTON (temperature setting V) and the BUTTON (temperature
setting W).
4. During group control, when setting by each indoor unit (mode No. 20, 22 and 23 have been selected), press the
BUTTON (unit no.) and select the INDOOR UNIT NO. to be set. (This operation is unnecessary when setting by
group.)
5. Press the BUTTON (set A) and select FIRST CODE NO.
6. Press the BUTTON (set B) and select SECOND CODE NO.
7. Press the BUTTON (set/cancel) once and the present settings are SET.
8. Press the BUTTON (field set) to return to the NORMAL MODE.
(Example) If during group setting and the time to clean air filter is set to FILTER CONTAMINATION - HEAVY, SET
MODE NO. to "10", FIRST CODE NO. to "0", and SECOND CODE NO. to "02".