3.2.4 Setting of Refrigerant Additional Charging Operation
When additional refrigerant is not charged all with outdoor unit in stop mode, operate the
outdoor unit and charge the liquid refrigerant from the service port of liquid stop value. The
additional charging operation is activated by pushbutton switch on the outdoor unit PC board.
[Additional refrigerant charge total flow]
Confirm LIQ & SUCTION a nd
Oil equalizing Stop valve closed.
Isall refrigerant charged?
Isall refrigerant charged?
YES
YES
NO
[Additi
ona
l
re
f
r
i
geran
t
c
h
arge
t
o
t
a
lfl
ow
]
Turn off the power.
Charge through Service port of
LIQ. Stop valve.
Open LIQ & SUCTION Stop
valve.
Open LIQUID Stop valve.
Disconnect charge hose.
END of charge method.
STOP refrigerant charge model
STEP 1
Additional
charge
without
Compressor
operation
Open Gas Stop valve.
(Liquid side stop valve : close
Oil equalizing valve : open
in case of multi outdoor
connection system.)
Start additional refrigerant
charge mode.
(Setting Mode 2 : Refer
operation procedure detail on
next page.)
STEP 2
Additional
charge
with
Compressor
operation
(V2892)