Daikin RXYQ16M7W1B [86/344] Operation mode

Daikin RXYQ16M7W1B [86/344] Operation mode
SiE39-404 Function general
Function 75
1.2 Operation Mode
Operation in
stop mode
Startup control
Oil return operation
Ye s
Ye s
No
No
Malfunction/Standby
Indoor unit stop or
thermostat OFF
Normal operation
• Compressor PI control
• Motorized valve PI control
• Protection control
Indoor unit thermostat ON
No
Ye s
Defrosting operation
Indoor unit thermostat ON
*)
Malfunction/Standby
Operation in
stop mode
Indoor unit stop or
thermostat OFF
Pressure
equalization
prior to startup
Indoor unit stop or
thermostat OFF
Restart standby
(Compressor stop)
Malfunction/
Standby
Indoor unit stop or
thermostat OFF
Pump-down
residual
operation
• Cooling startup
control
• Heating startup
control
Outdoor unit
rotation
Cooling or heating
operation
Malfunction/
Standby
Oil return IN
conditionsare met.
Defrost IN
conditionsare met.
Temperature
control change
In the event indoor unit stops or the thermostat
turns OFF while in oil return operation or
defrosting operation, pump-down residual
operation is performed on completion of the oil
return operation or defrosting operation.
Outdoor unit
rotation