Troubleshooting by Indication on the Remote Controller SiE39-404
226 Troubleshooting
Troubleshooting
(V2824)
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Caution
Replace the outdoor unit PC
Board (A1P).
C/H SELECT isset to "IND".
Cool / heat selection is
unified.
C/H SELECT
isset to "MASTER."
C/H SELECT
isset to "SLAVE."
Check
and see if the following items
are normal.
Doesa
malfunction occur when
the cool / heat selector is
set to "IND?"
Set C/H SELECT to "IND."
Fix the outdoor units multi
connection transmission
wiring and reset power.
Is the
outdoor units m
ulti
connection transmission
wiring normal?
Is the
indoor / outdoor unit
transmission wiring
normal?
Fix the indior / outdoor unit
transmission wiring.
The cool / heat unified
address for outdoor units in
outdoor - outdoor unit
transmission is duplicated.
Set the address correctly.
Replace the outdoor unit
ou
tside control adaptor.
repla
cement
Replace the outdoor unit PC
board (A1P).
Outdoor unit outside control adaptor
Is there continuity?
Does the cool/heat unified address match?
Outdoor unit (unified master unit)
Is there continuity?
Does the cool/heat unified address match?
Fix the problem.
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO