SiE39-404 Troubleshooting by Indication on the Remote Controller
Troubleshooting 195
2.19 E9 Outdoor Unit: Malfunction of Moving Part of
Electronic Expansion Valve (Y1E, Y2E)
Remote
Controller
Display
E9
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Check disconnection of connector
Check continuity of expansion valve coil
Malfunction
Decision
Conditions
Error is generated under no common power supply when the power is on.
Supposed
Causes
Defect of moving part of electronic expansion valve
Defect of outdoor unit PC board (A1P)
Defect of connecting cable
Troubleshooting
(V3067)
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
YES
YES
Caution
Return to normal?
Turn power supply off, and
turn power supply on again.
Electronic
expansion valve is
connected to X26A and
X28A of outdoor unit
PC board
(A1P).
Normal
when coil
check (1) of the moving
part of the electronic
expansion valve is
checked.
The connecting
cable isshort-circuited or
disconnected.
Replace the connecting cable.
Replace outdoor unit PC board
A1P.
NO
Replace the moving part of the
electronic expa
nsion valve.
External factor other than
malfunction (for example, noise
etc.).
After connecting, turn the power
off and then back on again.
* X26A only for RXYQ5M
YES
YES
NO
NO
NO