Daikin RXYQ16M7W1B [200/344] E3 outdoor unit actuation of high pressure switch

Daikin RXYQ16M7W1B [200/344] E3 outdoor unit actuation of high pressure switch
SiE39-404 Troubleshooting by Indication on the Remote Controller
Troubleshooting 189
2.14 E3 Outdoor Unit: Actuation of High Pressure Switch
Remote
Controller
Display
E3
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Abnormality is detected when the contact of the high pressure protection switch opens.
Malfunction
Decision
Conditions
Error is generated when the HPS activation count reaches the number specific to the operation
mode.
Supposed
Causes
Actuation of outdoor unit high pressure switch
Defect of High pressure switch
Defect of outdoor unit PC board
Instantaneous power failure
Faulty high pressure sensor
Troubleshooting
H1: Actuation of high pressure switch (HPS)
The outdoor unit PC board’s connector is disconnected.
Is the outdoor unit heat exchanger dirty?
Defect of outdoor fan
Is the refrigerant over-charged?
Faulty high pressure sensor
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Caution
Operation
is normal when turned
on again by remote
controller.
Replace outdoor unit PC board
A1P.
Actuation of high pressure switch.
H1
There was an instantaneous
power failure or a past safety
device actuated. Re-check
refrigerant system.
Contact
S1PH or S2PH
is open.
Connect the connector and
operate again.
Are the HPS
connectors connected
to the outdoor main
P.C.Board?
H1
NO
NO
NO
YES
YES
YES
(V3065)