Daikin RXYQ16M7W1B [280/344] Wiring diagrams for reference

Daikin RXYQ14M7W1B [280/344] Wiring diagrams for reference
SiE39-404 Wiring Diagrams for Reference
Appendix 269
2. Wiring Diagrams for Reference
2.1 Outdoor Unit
RXYQ5MY1B
L1-RED
A1P
A2P
A3P
A4P
BS1~5
C1, 4
DS1, 2
E1HC
F1U
F1U, 2U
H1P~8P
HAP
K1M
K1R
K2R
K3R
K6R
Printed circuit board (Main)
Printed circuit board (INV)
Printed circuit board (Fan)
Printed circuit board (Noise filter)
Push button switch
(mode, set, return, test, reset)
Capacitor
Dip switch
Crankcase heater
Fuse (250V, 5A, ) (A4P)
Fuse (250V, 10A,
) (A1P)
Pilotlamp (Service monitor-orange)
[H2P] prepare, test ------- flickering
malfunction detection ---- light up
Pilot lamp (Service monitor-green)
Magnetic contactor (M1C)
Magnetic relay
Magnetic relay (K1M)
Magnetic relay (Y1S)
Magnetic relay (Y2S)
K9R
K11R
K13R
L1R
M1C
M1F
PS
Q1RP
R1
R10
R133
R3, 4
R1T
R1T
R2T
R3T
R4T
R5T
S1NPH
S1NPL
Magnetic relay (Y4S)
Magnetic relay (Y3S)
Magnetic relay (E1HC)
Reactor
Motor (Compressor)
Motor (Fan)
Switching power supply
Phase reversal detect circuit
Resistor (Current limiting)
Re
s
istor (Current sensor)
Resistor (Current sensor)
Resistor
Thermistor (Air) (A1P)
Thermistor (Fin) (A2P)
Thermistor (Suction)
Thermistor (M1C discharge)
Thermistor (Heat exc. deicer)
Thermistor (Heat exc. outlet)
Pressure sensor (High)
Pressure sensor (Low)
S1PH
T1R
V1CP
V1R
V1R
X1M
X1M
Y1E
Y1S
Y2S
Y3S
Y4S
Z1C~5C
Z1F
Cool/Heat selector (KRC19-26A)
S1S
S2S
Pressu
re
switch (High)
Transformer (220-240V/20V)
Safety devices input
Power module (A2P)
Power module (A3P)
Ter mi nal strip (Power supply)
Ter mi nal strip (Control) (A1P)
Electronic expansion valve
Solenoid valve (Hot gas)
Solenoid valve
(
Receiver gas purge
)
Solenoid valve (4 way valve)
Solenoid valve (injection)
Noise filter (Ferrite core)
Noise filter (With surge absorber)
Selector switch (Fan/Cool • Heat)
Selector switch (Cool/Heat)
L2-WHT L3-BLK N-BLU
Power supply
380-415V 3N~50Hz
Detail of M1C
Notes:
1. This wiring diagram isapplied only to the outdoor unit.
2. : Field wiring.
3. : Terminal strip : Connector : Terminal : Protective earth (Screw)
4. When using the option adaptor, refer to the installation manual.
5. Refer to the installation manual, for connection wiring to indoor-outdoor
transmission F1 • F2, outdoor-outdoor transmission F1 • F2.
6. Refer to Operation cauton label (on switch box cover), how to use BS1~BS5 a
nd D
S1 • 2 switch.
7. When operation, dont short circuit for protection device. (S1PH)
8. Colors BLK: black, RED: red, BLU: blue, WHT: white, PNK: pink, YLW: yellow, BNR: brown, GRN: green,
ORG: orange.
(Back)
Switch box
(Front)
Note: 5
Outdoor (F1) (F2)
Indoor (F1) (F2)
Cool
Cool
Heat
S2S
Heat
S1S
Fan
Cool/Heat selector (Optional accessory)
Cool/Heat selector In-Out
Out-Out
3D038590E

Содержание

Скачать