Daikin RXYQ16M7W1B [187/344] Troubleshooting

Daikin RXYQ16M7W1B [187/344] Troubleshooting
Troubleshooting by Indication on the Remote Controller SiE39-404
176 Troubleshooting
Troubleshooting
(V2778)
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Caution
Replace float switch.
Modify the float switch's
connection and turn on again.
Connect the drain pump and
turn on again.
Check the drain piping for
clogging or upward slope, etc.
Replace indoor unit PC board.
Replace the drain pump or
check for dirt, etc.
Connect either ashort circuit
connector or float switch and
turn on again.
Defect of indoor unit PC board.
Loose connection of connector.
NO
The float
switch cont
act is
forming ashort circuit
(continuity check
with X8A or X15A
disconnected)
Provide 220~240V power
supply.
Is power supply
220~240V provided?
The float
switch is connected to
X8A of the indoor unit
PC board.
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO NO
NO
NO
NO
NO
Water buildsup
in the drain pan.
The drain
pump is connected
to X25A or terminals Y1
and Y2 of the
indoor
unit PC
board.
The dr
ain
pump works when
the power supply is reset
for the indoor
unit.
The voltage
of terminals Y1
and Y2 or X25A is
220~240 V (within
5minutes of resetting
the power
supply).
NO
NO
YES
The float switch
functions normally.
Becomes
normal when X8A of
the indoor unit PC board
isshort circuited
A short
circuit connector is
connected to
X8A.