SiE39-404 Troubleshooting by Indication on the Remote Controller
Troubleshooting 201
2.24 J2 Current Sensor Malfunction
Remote
Controller
Display
J2
Applicable
Models
RXYQ5~48M
Method of
Malfunction
Detection
Malfunction is detected according to the current value detected by current sensor.
Malfunction
Decision
Conditions
When the current value detected by current sensor becomes 5A or lower, or 40A or more during
standard compressor operation.
Supposed
Causes
Faulty current sensor
Faulty outdoor unit PC board
Troubleshooting
(V3071)
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Caution
NO
NO
YES
YES
Is the
current sensor
mounted on the T-phase
wire?
Is the
connector for
current sensor
connected to X30A, X31A
on outdoor unit
PC board
(A1P)?
Replace current sensor and outdoor
unit PC board.
Connect the connector, and
operate unit again.
Mount the current sensor correctly,
and operate unit again.