Daikin RXYQ10PY1 [420/487] Wiring adaptor for electrical appendices 1

Daikin RXYQ5PY1 [420/487] Wiring adaptor for electrical appendices 1
Adaptor ED34-645B
812 Control
5.2 <KRP2A61 / KRP2A62 / KRP2A53>
Wiring Adaptor for Electrical Appendices (1)
5.2.1 System Configuration
The KRP2A61·62 enables operation by remote control (ON/OFF control, temperature setting, operation display, error
display). With it, the following system can be built. Note however that the adaptor cannot be used with other optional
controllers for centralized control.
1. Zone Control
(Unified control of a max. 64 groups of a max. 16 indoor units each. But, the max. of indoor units is 128.)
This system requires the following parts.
Wiring Adaptor for Electrical Appendices (1)
... KRP2A61 or KRP1C62
Remote controller switches (For control)
(Ex.) Zone control for 8 FXC63LVE units (control groups of 4, 3 and 1)
Note:
1. Individual indoor units connected to the centralized line cannot be displayed individually.
2. For wiring adaptor for electrical appendices (2) <KRP4A51, 52, 53, 54>, refer to page 819.
C : 1PA63641G
...BRC1C62
BRC2A51
BRC3A61
Per group
KRP2A61×1 kit
BRC1C62×3 kits
1 set required for each group.